Routine starting procedure – SPX Cooling Technologies MARLEY CLASS 800 User Manual

Page 8

Advertising
background image

8

Routine Starting Procedure

After periods of routine shutdown, the following restarting procedure should
be followed:

• Start the circulating water pump(s). Increase the flow of circulating water

gradually to design water rate to avoid surges or water hammer which could
damage the distribution piping.

Circulating cold water over a tower in freezing weather will cause ice
to form, which may cause damage to the fill system. Water should be
bypassed directly to the cold water basin until the heat load causes
its temperature to rise above 70°F (21°C), at which time it may be
directed over the tower. Also, towers must not be operated with
reduced water rate and/or no heat load during freezing weather. If
a bypass is used, Do Not modulate.

• Start the fan(s). On multi-cell towers, only as many fans should be started as

are needed to produce the desired cold water temperature. If the tower is
equipped with two-speed motors, fans may be progressively started at half
speed, increasing to full speed as necessary to maintain the desired cold
water temperature. (See Temperature Control and Energy Management
on pages 13 and 14.)

Caution

Advertising