Intake air connection, Breathing hazard - carbon monoxide gas, Intake air screen – State Industries ULTRA FORCE 101 User Manual

Page 26: Intake air condensate tee installation

Advertising
background image

26

14. if installing 3 inch intake air pipe connect the intake air pipe to

the intake air connection on the water heater.

15. if installing 4 inch intake air pipe transition to 3 inch pipe at

the intake air connection on the water heater as shown in

Figure 20. The field installed 3” pipe between the intake air

connection and the 4” x 3” reducer coupling should be 18

inches (45 cm) or less in length.

3” PIPE FACTORY

INSTALLED

4” PIPE FIELD

SUPPLIED

3” PIPE FIELD

SUPPLIED

4” x 3” REDUCER

FIELD SUPPLIED

3” COUPLING OR TEE

FACTORY INSTALLED

INTAKE AIR CONNECTION

INTAKE AIR CONNECTION

INTAKE AIR

COMBUSTION

BLOWER

figure 20

INSTALL TEE FITTING AS CLOSE TO WATER HEATER

INTAKE AIR CONNECTION AS POSSIBLE

INTAKE AIR CONDENSATE TEE INSTALLATION

FIELD SUPPLIED

3” x 3” x 1/2” TEE

WITH HOSE BARB

FITTING INSTALLED

FACTORY

INTAKE AIR

CONNECTION

INTAKE

AIR

PIPING

CONNECT FIELD

SUPPLIED FLEXIBLE

DRAIN HOSE TO BARB

FITTING AND FORM A

LOOP WATER TRAP IN

DRAIN HOSE

RUN DRAIN HOSE

TO SUITABLE FLOOR

DRAIN SEPARATELY

FROM OTHER

CONDENSATE DRAINS

figure 21

11. if installing 3 inch vent pipe connect the vent pipe to the

exhaust elbow on the water heater.

12. if installing 4 inch vent pipe transition to 3 inch pipe at the

exhaust elbow on the water heater as shown in Figure 18 on

page 25. The field installed 3” pipe between the exhaust elbow

and the 4” x 3” reducer coupling should be 18 inches (45 cm)

or less in length.

13. Ensure the intake Air Screen on the intake Air Connection to

the water heater is removed before connecting the intake air

pipe to the water heater. See Figure 19.

Do not obstruct water heater air intake.

Gas and carbon monoxide detectors

are available.

Install water heater in accordance with

the instruction manual.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Breathing Hazard - Carbon Monoxide Gas

note: Do not leave the screen inside the intake Air

Connection for Direct Vent installations. Once the intake

air pipe is installed the screen will be hidden from view and

may become clogged with debris over time. This will cause

improper combustion and may also lead to blocked intake

Air fault conditions and associated control system lock outs.

INTAKE AIR SCREEN

(remove for Direct Vent)

120,000 & 150,000

Btu/hr MODELS

199,000 & 250,000

Btu/hr MODELS

3 INCH INTAKE AIR CONNECTIONS

FACTORY INSTALLED

INTAKE AIR SCREEN

figure 19