See figure 57 – State Industries ULTRA FORCE 101 User Manual

Page 53

Advertising
background image

53

8. Compare the actual supply gas pressure reading recorded

above to the required minimum/maximum values given

in Table 3 on page 12. Adjust supply gas pressure

as necessary, see Supply Gas Pressure Adjustment on

page 54.

9. When complete turn off gas to the water heater, see

instructions on page 55. Disconnect manometers

and replace all pipe plugs removed for testing. Ensure

all test port needle valves opened during testing are

completely closed.

MANIFOLD GAS

PRESSURE

TEST PORT

SUPPLY GAS

PRESSURE

TEST PORT

GAS VALVE / VENTURI ASSEMBLY TOP VIEW

199,000 & 250,000 Btu/hr MODELS

VENTURI

COMBUSTION

AIR INLET

GAS

VALVE

COMBUSTION

BLOWER

CONNECTION

figure 59

MANIFOLD GAS

PRESSURE

TEST PORT

SUPPLY GAS

PRESSURE

TEST PORT

GAS VALVE TOP DETAIL VIEW

199,000 & 250,000 Btu/hr MODELS

figure 60

GAS VALVE / VENTURI ASSEMBLY SIDE VIEW

199,000 & 250,000 Btu/hr MODELS

VENTURI

LOW GAS

PRESSURE

SWITCH

SUPPLY GAS

CONNECTION

GAS

VALVE

COMBUSTION

AIR INLET

figure 61

lighting the water heater
1. SUF 120 & 150 models: turn the on/off switch on the gas

valve to the "on" position, see Figure 57 and Figure 58.

2. Turn the water heater’s on/off switch to the “on” position.
3. Wait for the control system to complete its boot up sequence.

The Desktop screen showing the current Operating Set

Point and Tank Temperature will be displayed on the control

system’s LCD when the boot up sequence is complete.

4. Using the control system menus and Uim (user interface

module), change the Operating Set Point to a setting higher

than the current tank temperature displayed on the control

system LCD plus the Differential setting to activate a call for

heating. See Control System Operation on page 44.

ON

OFF

MANIFOLD GAS

PRESSURE REGULATOR

COVER SCREW

GAS VALVE TOP VIEW

120,000 & 150,000 Btu/hr MODELS

MANIFOLD GAS

PRESSURE TAP

1/8’ NPT PLUG

SUPPLY GAS

PRESSURE TAP

1/8’ NPT PLUG

INLET

OUTLET

ON/OFF

SWITCH

figure 57

5. record the manifold gas pressure when the 24 Volt Gas Valve

is energized and the main burner is ignited, the animated gas

valve icon will be displayed on the Desktop screen of the

control system’s LCD when the control system energizes the

24 Volt Gas Valve, a animated flame icon will appear when

main burner ignition is successful, see the Status icons

descriptions in Table 11 on page 45.

GAS VALVE SIDE VIEW

120,000 & 150,000 Btu/hr MODELS

MANIFOLD GAS

PRESSURE TAP

1/8’ NPT PLUG

SUPPLY GAS

PRESSURE TAP

1/8’ NPT PLUG

BOTTOM OF TEE

1/8” NPT

TEE FITTING

GAS VALVE

OUTLET

ON/OFF

SWITCH

LOW GAS

PRESSURE

SWITCH

figure 58

6. Compare the actual manifold gas pressure reading recorded

above to the required minimum/maximum values given in Table

3 on page 12. Adjust manifold gas pressure as necessary,

see manifold Gas Pressure Adjustment on page 54.

7. record the supply gas pressure when the 24 Volt Gas Valve is

energized and the main burner is ignited. This is a “dynamic”

gas pressure reading; while the water heater is firing.