Configuration code (cfg), Software version (soft), Element test (test) – Sentry Industries Sentry 2.0 User Manual

Page 21: Reset (rst), Zone temperature, Difference (diff), Two zone kilns: adjust heat in, Center section (cadj), Zone temperatures (t123), Multiple zone options

Advertising
background image

Configuration Code (CFG)

Information for Technicians

From

IdLE

, press OPTIONSrepeatedly until

CFG

ap-

pears. Press ENTER. The factory configuration code will ap-

pear. Press ENTER. Press STOP to return to

IdLE

. The

configuration code can be changed only at the factory.

Software Version (SOFT)

Information for Technicians

From

IdLE

, press OPTIONSrepeatedly until

SOFT

ap-

pears. Press ENTER. The software version will appear. Press

ENTER. Press STOP to return to

IdLE

. The software ver-

sion can be changed only at the factory.

Element Test (TEST)

Test the Heating Elements and Relays

This test is useful when measuring the wall receptacle

voltage under load, and amperage with an ammeter. On a

multiple zone kiln, the test helps determine if the relays and

thermocouples are wired to the correct zones. If you test

thermocouples with a lighter or other heat source, use the

Test option.
Single Zone Kiln

1 From

IdLE

, press OPTIONSrepeatedly until

TEST

appears.

2 Press ENTER.

POWR

will appear, alternating with

kiln temperature. The elements will turn on for 2

minutes. Press any key to abort the test.

Multiple Zone Kiln

1 From

IdLE

, press OPTIONSrepeatedly until

TEST

appears.

2 Press ENTER.

TOP

will appear, alternating with

the temperature of the top zone. The elements will

turn on for 2 minutes. Then

MID

will appear, with

temperature for the middle zone, and

BOT

with

temperature for the bottom zone. (A 2 zone kiln

shows

TOP

and

BOT

displays only.)

3 During the 2 minute test, press any key to end a zone

test. The controller will then begin to test the next

zone.

AOP Outlet

After the above tests, kilns equipped with the AOP outlet

will display

J3-3

for 2 minutes to test power to the AOP

outlet.

Reset (RST)

Reset the Controller to Most Factory Defaults:

Perform Only When Requested by a Technician

Reset does the following:

Selects Type-S thermocouple

Selects °F

Erases Cone offsets

Erases Thermocouple offset

Erases user programs in Ramp-Hold

CAUTION: If your kiln uses a Type-K thermocou-

ple, the Sentry will underfire after a reset! Use the

Thermocouple Option (page 19) to select Type-K

again.

1 From

IdLE

, press OPTIONSrepeatedly until

RST

appears.

2 Press ENTER. Use the 1 or 2 key to select

NO

or

YES

.

3 After selecting one of the above, press ENTER. Press

STOP to return to

IdLE

.

Multiple Zone Options

These options appear only on multiple zone kilns.

Zone Temperature Difference (DIFF)

View Maximum Temperature Spread

For a 2 zone kiln, this option shows temperature differ-

ence between the zones. For a 3 zone kiln, it shows the high-

est temperature difference between any two zones. If the

temperature shown is larger than expected, go to option T

123 to view the temperature of each zone.

1 Press OPTIONS repeatedly until

DIFF

appears.

Press ENTER.

3 The maximum difference in temperature between

any zones displays. (Example:

-003

.)

Two Zone Kilns: Adjust Heat in

Center Section (CAdJ)

The Center Adjust option appears only on 2 zone kilns

that contain 3 relays and 3 banks of elements. It does not ap-

pear on 2 zone kilns with 2 relays, or on 3 zone. The Center

Adjust acts as an infinite control switch that adjusts heat to

the center section of the kiln. A number will display. 100 is

the factory default, meaning 100% heat. You can change the

setting from 0 to 200. The higher the number, the more the

heat in the center section.

1 From

IdLE

, press OPTIONSrepeatedly until

CAdJ

appears.

2 Press ENTER. Use any number key to change the

number that appears.

3 Press ENTER. Press STOP to return to

IdLE

.

Zone Temperatures (T123)

View Temperature of Each Zone

1 Press OPTIONS repeatedly until

T123

appears.

Press ENTER.

3 The temperature for each zone will display one after

the other, cycling for one minute. Then normal tem-

perature display will return. For example:

Top zone:

TC 1¯ 1250

Middle zone:

TC 2- 1251

Bottom zone:

TC 3_ 1249