CONNECTION

CONNECTIONS TO THE ALARM IN AND RS232C/RS485 TERMINALS

[A] RS485 (RJ-11) terminal connection

Make the connection to the RS485 control terminal using a
modular cable (sold separately).

If using a straight type cable, connect it between the A
terminals, or between the B terminals (see illustration below).

If using a crossed type cable, connect it from the A terminal
to the B terminal, or from the B terminal to the A terminal (see
illustration below).

[B] Using the push-lock terminals

Make the connections to pins A, B, C (earth) of the CONTROL
terminal using a twisted-pair cable (sold separately). Then,
connect signal A to A, and signal B to B.

[C] SENSOR ALARM OUT terminals

When the unit internal video sensor send a trigger, it will be
output at the SENSOR ALARM OUT terminals. By connecting
indicator lamps switching circuits to theses connectors (Fig. 1),
an indication can be generated when the video sensors send a
trigger.
For example, the video sensor alarm indicator lamps could be
laid out on a factory floor plan to give accurate indication of
trigger location. The terminals are normally open (NO). A trigger
at the video sensor for one of the cameras, will switch the signal
to LOW.

Connect a 9-pin D-SUB cable (sold
separately) from the RS232C terminal on the
rear panel to the computer serial connector.

1

2

A

B

RS485

MONITOR

To terminal A

To terminal A

Straight-type cable

Cross-type cable

Straight type

1

6

Cross type

1
2
3
4
5
6

1
2
3
4
5
6

Not used

Not used

Not used

Not used

1
2
3
4
5
6

Not used

Not used

Not used

Not used

1
2
3
4
5
6

1

6

1

6

1

6

RS232C

C A B C AL C R1 R2 C SW C

Push in to insert cable

Twisted-pair cable

To A signal

To B signal

Ground

Fig. 1

Rating values for each connector (at 25˚C)

Maximum current : 25mA

Maximum voltage : 25V

Maximum power : 40mW

1K

RS232C

1 2 3 4 5 6 7 8 9 10 11 12 13 1415 16

C

C A B C AL C R1 R2 C SW C

A

B

RS485

ALARM IN

CONTROL

SENSOR ALARM
OUT

Computer

9-pin D-SUB cable
(sold separately)

External alarm sensors

(door bell, interphone, etc.)

Alarm input
terminal

Switching output
terminal

[A]

[B]

[C]

Common

Common

Common