Auxiliary circuit breaker electrical work – Samsung A6 User Manual

Page 38

Advertising
background image

E-

38

I

NSTALLING THE

O

UTDOOR

U

NIT

Auxiliary Circuit Breaker

Electrical Work

1

The supply voltage must be the same as the rated voltage of the
air conditioner.

2

Prepare the power souce for exclusive use with the air conditioner.

3

Use 15 amperes time delay fuse or circuit breaker.

➢ When using the special NFB, use the NFB to bear the capacity of the

air conditioner.

➢ Otherwise, the shot circuit in the NFB may occur.

Outdoor unit

Distribution

board

Auxiliary

power s/w

Auxiliary circuit breaker should be installed near outdoor unit so

that each access is possible. Main/outdoor power supply cable are
connected to upper/lower terminal of auxiliary circuit breaker.

It is necessary that the conduit kit for power supply to the outdoor

unit be installed between auxiliary power S/W and the outdoor
unit. (the conduit kit is optional)

MODEL

AS09

✴✴MA AS12✴✴MC

Power supply

Power cable

Assembly cable

Operating current(C)

Starting Current

Power consumption (C)

115V~/60Hz

Single phase

AS07

✴✴MA

115V~/60Hz

Single phase

3G AWG 14

2G AWG 14 + 2G AWG 18

31A

1320W

47A

32A

6.1

8.5

6.4

900W

680W

208-230V~/60Hz

Single phase

MODEL

AS18

✴✴RC

AS24

✴✴RC

Power supply

Power cable

Assembly cable

Operating current(C)

Starting Current

Power consumption (C)

208-230V~/60Hz

Single phase

3G AWG 12

3G AWG 14 + 2G AWG 18

4G AWG 14 + 2G AWG 18

2350W

35A

1900W

10.5A

10.5A

8.6A

208-230V~/60Hz

Single phase

❊ The designs and shape are subject to

change according to the model.