TUBULAR UNIT HEATER
HIGH ALTITUDE DERATION
This Tubular Unit Heater has been manufactured utilizing
standard burner orifi ces and a normal manifold pressure
setting as per the specifi cations shown on your unit rating
plate.

All unit deration must be done through fi eld adjustments
by a qualifi ed technician. Once the proper adjustments
are made in the fi eld, attach label #J17-06459 to the unit,
and record adjusted manifold pressure, altitude of the
unit installation and the technician’s name and date on
the label using a permanent marker.

Refer to Installation Instruction section on Adjustments-
Gas Input Rate for adjusting the manifold pressure.

Manifold

Pressure

(In. W.C.)

PROPANE (LP) GAS

NATURAL GAS

Heating*

Value

BTU/Cu. ft.

Altitude

(Feet)

8.6

8.5

8.4

8.4

8.3

8.2

8.1

8.0

7.9

7.7

7.6

7.5

7.4

7.2

7.1

6.9

6.8

2,000

2,500

3,000

3,500

4,000

4,500

5,000

5,500

6,000

6,500

7,000

7,500

8,000

8,500

9,000

9,500

10,000

*Notes:
1. Consult local utility for actual heating value.
2. Tables based on heating value of 1,050 BTU/Cu. ft. at sea level.

2,278

2,237

2,196

2,156

2,116

2,077

2,039

2,000

1,964

1,927

1,891

1,853

1,817

1,781

1,745

1,709

1,673

Table 5A

Manifold

Pressure

(In. W.C.)

Heating*

Value

BTU/Cu. ft.