Electrical connections – Sterling TF-300 User Manual

Page 9

Advertising
background image

9

HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC
POWER INCLUDING REMOTE
DISCONNECTS BEFORE
SERVICING. Failure to
disconnect power before
servicing can cause severe
personal injury or death.

Standard units are shipped for use on 115 volt, 60 hertz,
single phase electric power. The motor name-plate and
electrical rating of the transformer should be checked
before energizing the unit heater electrical system. All
external wiring must conform to the latest edition of
ANSI/NFPA No. 70, United States National Electrical
Code, and applicable local codes; in Canada, to the
Canadian Electrical Code, Part 1, CSA Standard C22.1.

Do not use any tools (i.e. screwdriver,

pliers, etc.) across terminals to check for power. Use
a voltmeter.

It is recommended that the electrical power supply to
each unit heater be provided by a separate, fused, and
permanently live electrical circuit. A disconnect switch of
suitable electrical rating should be located as close to
the gas valve and controls as possible. Each unit heater
must be electrically grounded in accordance with the
latest edition of the United States National Electrical
Code, ANSI/NFPA No. 70, or CSA Standard C22.1. Refer
to Figures 5a, 5b, 5c, 5d and 5e.

THERMOSTAT WIRING AND LOCATION:

NOTICE: The thermostat must be mounted on a
vertical, vibration-free surface, free from air currents,
and in accordance with the furnished instructions.

Mount the thermostat approximately 5 feet (1.5m) above
the floor, in an area where it will be exposed to a free
circulation of average temperature air. Always refer to
the thermostat instructions, as well as our unit wiring
diagram, and wire accordingly. Avoid mounting the
thermostat in the following locations:
1. Cold Areas - Outside walls or areas where drafts

may affect the operation of the control.

2. Hot Areas - Areas where the sun's rays, radiation,

or warm air currents may affect the operation of
the control.

3. Dead Areas - Areas where the air cannot circulate

freely, such as behind doors or in corners.

ELECTRICAL CONNECTIONS

Figure 5a -
Low-voltage T
Thermostat Wiring
Single Stage

Figure 5b -
Low-voltage
Thermostat Wiring
Two Stage

Figure 5c -
T834H-1009 or
T834H-1017
Thermostat Wiring

THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS:
The initial heat anticipator setpoint should equal the
thermostat's current amperage draw when the unit is
firing. This setpoint should be measured for the best
results. Use the recommended ranges for a guide. If
further information is needed, consult your thermostat
manufacturer's instructions.

Recommended heat anticipator settings:

Unit Size:

30 thru 200

250 thru 400

For Tubular Units:

0.35 Amps

0.65 Amps

NOTICE: The start-up fan delay should not exceed
30 seconds from a cold start.

IMPORTANT: For all wiring connections, refer to the
wiring diagram shipped with your unit (either affi xed
to the side jacket or enclosed in the installation
instructions envelope). Should any original wire
supplied with the heater have to be replaced, it
must be replaced with wiring material having a
temperature rating of at least 105° C.

Should any high limit wires have to be replaced,
they must be replaced with wiring material having a
temperature rating of 200° C minimum.

R G W1 W2

W

R

G

Honeywell

T834H-1009

or

T834H-1017

Thermostat

D6922B

Advertising
This manual is related to the following products: