Table 6 - Tubular Propeller Troubleshooting with LED Indicator Assistance

No Cycling or appliance power
or ther mostat call for heat
since appliance failure has
occured.

Line voltage power can
cause product damage,
severe injury or death.
Only a trained experienced
service technician should
perform this trouble-
shooting.

1. Check the system thermo-

stat to make sure it is call-
ing for heat. (Do not cycle
the thermostat on and off at
this time.)

2. Remove the appliance

burner compartment door.
Do not interrupt power
to the control board by
opening any electrically
interlocked panels.

3. Observe the LED indicator

on the control board (a
greem LED labeled “OK”
indicates system faults);
check and repair system
as noted in the chart to the
right.

*NOTICE: Air flow proving
switch and power ventor
hose barbs must be free
of any dust or debris at all
times. Periodically check
these openings and/or if any
problems occur.

Not

Applicable

Not

Applicable

1.

Line voltage on terminals 120
and C on transformer.

2.

Low voltage (24V) on terminals
24 and C on transformer.

3.

5 Amp fuse on circuit board.

1. Common side of transformer

grounded to chassis.

2. Loose spark ignitor.

1. Gas supply off or gas supply

pressure too low.

2. Flame sense rod contaminated

or loose wire.

3. Gas valve switch is off or wires

are not connected.

4. Broken or cracked porcelain on

fl ame probe or spark ignitor.

1. Obstructions or restrictions

in appliance air intake or fl ue
outlet are preventing proper
combustion airfl ow.

2. Moisture or debris in tubing that

connects pressure switch and
draft inducer.

3.

Airfl ow switch jumpered or
miswired.

1. Open manual reset rollout switch.
2.

Gas pressure too high, over fi re
condition.

3.

Incorrect airfl ow due to blockage
or motor not operating.

1. Flame probe miswired

or shortened.

1. Thermostat is interfering

with control board.

Control OK, no call for heat.

Control OK, call for heat present.

Internal control fault, or no power.

Control internal failure or bad ground.

In lockout from failed ignitions
or fl ame losses.

Pressure Switch open with inducer on
or closed with inducer off.

Limit or rollout switch is open.

Flame sensed while gas valve is off.

On-board microprocessors disagree.

LED STATUS

INDICATES

CHECK/REPAIR

Slow Flash

Fast Flash

Steady Off

Steady On

2 Flashes

3 Flashes

4 Flashes


5 Flashes


6 Flashes