Pipe installation – Sterling TF-300 User Manual

Page 8

Advertising
background image

8

PIPE INSTALLATION

Figure 4 - Pipe Installation, Standard Controls

Never use an open fl ame to detect

gas leaks. Explosive conditions may exist which
may result in personal injury or death!

The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system in excess of 1/2 psig
(3.5 kPa).

The appliance must be isolated from the gas supply
piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).

Table 4 - Gas Piping Requirements

SINGLE STAGE GAS PIPING REQUIREMENTS*

GasType

Natural Gas

Propane (LP) Gas

Manifold

3.5 in. W.C.

10.0 in. W.C.

Pressure

(0.9 kPa)

(2.5 kPa)

14.0 in. W.C. Max.

14.0 in. W.C. Max.

Supply Inlet

(3.5 kPa)

(3.5 kPa)

Pressure

5.0 in. W.C. Min.

11.0 in W.C. Min.

(1.2 kPa)

(2.7 kPa)

*For single stage application only at normal altitudes.

1. Install the gas piping in accordance with applicable

local codes.

2. Check gas supply pressure. Each unit heater must

be connected to a manifold pressure and a gas
supply capable of supplying its full rated capacity
as specified in Table 4. A field LP tank regulator
must be used to limit the supply pressure to a
maximum of 14 in. W.C. (3.5 kPa). All piping should
be sized in accordance with the latest edition of
ANSI Standard Z223.1, National Fuel Gas Code;
in Canada, according to CGA B149. See Tables
1 & 3 for correct gas piping size. If gas pressure
is excessive on natural gas applications, install a
pressure regulating valve in the line upstream from
the main shutoff valve.

3. Adequately support the piping to prevent strain on

the gas manifold and controls.

4. To prevent the mixing of moisture with gas, run the

take-off piping from the top, or side, of the main.

5. Standard Unit Heaters, optional two-stage units are

supplied with a combination valve which includes:

a. Manual "A" valve

b. Manual "B" valve

c. Solenoid valve

d. Pressure regulator

Pipe directly into the combination valve (see Figure
4).

6. Gas valve has a pressure test post requiring a

3/32" hex head wrench to read gas supply and
manifold pressures. Open 1/4 turn counterclockwise
to read, turn clockwise to close and reseat. A 5/16"
ID hose fi ts the pressure post.

7. Provide a drip leg in the gas piping near the gas

unit heater. A ground joint union and a manual gas
shutoff valve should be installed ahead of the unit
heater controls to permit servicing. The manual
shutoff valve must be located external to the jacket
(See Figure 4).

8. Make cer tain that all connections have been

adequately doped and tightened.

Do not over tighten the inlet gas

piping into the valve. This may cause stresses that
will crack the valve!

NOTICE: Use pipe joint sealant resistant to the
action of liquefied petroleum gases regardless of
gas conducted.

Check all pipe joints for leakage

using a soap solution or other approved method.
Never use an open flame or severe personal
injury or death may occur!

Advertising
This manual is related to the following products: