SDF 250/400/500

Start up 3-7

Hopper temp Target

Enter the drying temperature for the drying
hopper.

Hopper temp Act.

The current temperature at the feed opening of
hopper flap will be displayed.

&

If the unit operates with
motor flaps (optional):

Granule Temp

Enter the material temperature at which the flap
on the drying hopper should close.

&

This value is entered in
percent of the temperature
on the hopper inlet.
The material temperature
calculated by the control
system for closing the flap
on the drying hopper is
displayed

Drying time Target

Enter the dwelling time of the material within the
drying hopper in minutes.

F

Observe the indicated
dwelling time.

&

When the drying hopper is released, the dwelling time starts. The
residual time is displayed (= current dwelling time).
If the drying hopper is blocked, the current dwelling time is reset
to the value of the dwelling time which has been entered before.

Drying time Act

The dwelling time of the material in the drying hopper is displayed in minutes.

Displaying trend

Temperature