Smart-UPS X-Series Operation

Using the Controllable Outlet Groups and UPS outlets

The UPS outlets function as a master switch. They turn on first when power is applied, shut
off last when there is a power outage and battery run-time has been exhausted.

The UPS outlets must be turned on for the Controllable Outlet Groups to turn on.

1. Connect critical equipment to the UPS outlets (except for 1500 VA models; then, connect all

critical equipment to one Controllable Outlet Group.)

2. Connect peripheral equipment to the Controllable Outlet Groups.

– Nonessential equipment that should shut off quickly in the event of a power outage to

conserve battery runtime can be added to a short power-off delay

– If equipment has dependent peripherals that must restart or shut down in a specific order, such

as an ethernet switch that must restart before a connected server, connect the devices to
separate groups

– Equipment that needs to reboot independently from other equipment should be added to a

separate group

3. Use the Configuration menus to configure how the Controllable Outlet Groups will react in the

event of a power outage.

Customize the Controllable Outlet Groups and the UPS outlets

Use the Control menus to change the Controllable Outlet Groups and the UPS outlet settings.

Function

Factory Default Options

Description

Name String
Outlet Group

Outlet Group 1

Edit these names using an external interface, such as the Network
Management Card Web interface.

UPS Name String UPS Outlets

Turn On Delay

0 sec

0-32767 sec

The amount of time the UPS or Controllable
Outlet Group will wait between receiving the
command to turn on and the actual startup.

Turn Off Delay

0 sec

0-32767 sec

The amount of time that the UPS or
Controllable Outlet Group will wait between
receiving the command to turn off and the
actual shut down.

Reboot Duration 4 sec

0-32767 sec

The amount of time that the UPS or
Controllable Outlet Group must remain off
before it will restart.

Minimum Return
Time

0 sec

0-32767 sec

The amount of battery runtime that must be
available before the UPS or Controllable
Outlet Group will turn on.

Load Shed On
Battery

Disabled

• Shutdown with

Delay

• Shutdown

immediately

• Turn off

immediately

• Turn off with

delay

• Disabled

When the unit switches to battery power, the
UPS can disconnect power to the Controllable
Outlet Groups to save runtime.

Configure this delay time, use the

L

OAD

S

HED

T

IME

WHEN

O

N

B

ATTERY

setting.