Configuration

UPS Settings

Start-up Settings

Configure these settings at initial start-up, using the display interface or APC PowerChute

®

software.

Note: During start-up, use the display interface to configure these settings. If nothing is
selected, the until will use the default settings.

General Settings

Configure these settings at any time, using the display interface or APC PowerChute software.

Function

Factory Default Options

Description

Language

English

• English
• French*
• German*
• Spanish*
• Italian*

The language for the display interface.

*Language options will vary by model.

Local power
quality

Good

• Good
• Fair
• Poor

Select the quality of input utility power.
• If Good is selected, the unit will go on battery

power more often to provide the cleanest power
supply to the connected equipment.

• If Poor is selected, the UPS will tolerate more

fluctuations in power and will go on battery power
less often.
If unsure of the local power quality, select Good.

Menu Type

Standard

Standard or
Advanced

The advanced menus include all parameters. The
Standard menus display a limited set of menus and
options.

Display
Mode

Always On

Always On or
Power Saving

The display may be always on or may be set to
automatically turn on only when using the
configuration buttons or if an event occurs.

Function

Factory Default Options

Description

High transfer
point

120 V: 140 VAC

120 V: 140-150 VAC To avoid unnecessary battery usage, set the

transfer point higher if the utility voltage is
chronically high and the connected equipment
is known to work under this condition. This
setting may also be adjusted using the power
quality setting.

230 V: 280 VAC

230 V: 280-300 VAC

Low Transfer
Point

120 V: 75 VAC

120 V: 75-85 VAC

Set the transfer point lower if the utility
voltage is chronically low and the connected
equipment can tolerate this condition.This
setting may also be adjusted using the power
quality setting.

230 V: 170 VAC

230 V: 150-170 VAC