Smart-UPS X-Series Operation

10

Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC) and are set in
the factory. These settings can only be modified using an external interface, like the NMC web interface.

• NMC IP Address Mode

• NMC IP Address

• NMC Subnet Mask

• NMC Default Gateway

Load Shed Time
when On Battery

Disabled

0-32767 sec

The amount of time the outlets will function on
battery power before they will turn off.

Load Shed On
Runtime

Disabled

• Shutdown with

delay

• Shutdown

immediately

• Turn off

immediately

• Turn off with

delay

• Disabled

When the battery runtime falls below the
specified value, the Controllable Outlet Group
will turn off.

Configure this time using the

L

OAD

S

HED

R

UNTIME

R

EMAINING

setting.

Load Shed On
Runtime
Remaining

Disabled

0-32767 sec

When the remaining runtime reaches this level,
the Controllable Outlet Group will turn off.

Load Shed on
Overload

Disabled

• Disabled
• Enabled

(Applicable only for Controllable Outlet
Groups, not the UPS outlets.) When enabled,
the Controllable Outlet Group will turn off
immediately in the event of a power outage
and will have to be manually restarted.

Function

Factory Default Options

Description