Electrical data, 1. electrical characteristics – Sanyo STB1220C1 User Manual

Page 22

Advertising
background image

6. ELECTRICAL DATA

6-1. Electrical Characteristics

Model

STB0810C1

Model

STB1010C1

Model

STB1020C1

Model

STB1220C1

Outdoor Unit

Complete Unit

Fan Motor

Compressor

Performance at

230 / 208V 1-phase 60Hz

Rating Conditions

Running Amps.

A

0.61

/

0.64

5.49

/

5.96

6.1

/

6.6

Power Input

kW 0.142 / 0.132

1.208 / 1.198

1.35

/

1.33

Full Load Conditions Running Amps.

A

0.61

/

0.64

6.29

/

6.96

6.9

/

7.6

Power Input

kW 0.142 / 0.132

1.428 / 1.438

1.57

/

1.57

Rating Conditions

: Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.
Outdoor Air Temperature 95°F (35°C) D.B.

Full Load Conditions : Indoor Air Temperature 90°F (32.2°C) D.B. / 73°F (22.8°C) W.B.

Outdoor Air Temperature 110°F (43.3°C) D.B.

Outdoor Unit

Complete Unit

Fan Motor

Compressor

Performance at

230 / 208V 1-phase 60Hz

Rating Conditions

Running Amps.

A

0.61

/

0.64

4.39

/

4.66

5.0

/

5.3

Power Input

kW 0.142 / 0.132

0.998 / 0.978

1.14

/

1.11

Full Load Conditions Running Amps.

A

0.61

/

0.64

4.99

/

5.26

5.6

/

5.9

Power Input

kW 0.142 / 0.132

1.118 / 1.098

1.26

/

1.23

Outdoor Unit

Complete Unit

Fan Motor

Compressor

Performance at

115V 1-phase 60Hz

Rating Conditions

Running Amps.

A

1.26

9.34

10.6

Power Input

kW

0.145

1.055

1.20

Full Load Conditions Running Amps.

A

1.26

11.04

12.3

Power Input

kW

0.145

1.255

1.40

Outdoor Unit

Complete Unit

Fan Motor

Compressor

Performance at

115V 1-phase 60Hz

Rating Conditions

Running Amps.

A

1.26

7.04

8.3

Power Input

kW

0.145

0.795

0.94

Full Load Conditions Running Amps.

A

1.26

8.34

9.6

Power Input

kW

0.145

0.935

1.08

Cooling only models