2. defrosting operation (heating) – Sanyo STB1220C1 User Manual

Page 49

Advertising
background image

45

10-2. Defrosting Operation (Heating)

Defrosting Flowchart

Defrosting Mode Timing Chart

Once the air conditioner enters defrosting mode, it will not release defrosting until the

outdoor heat exchanger coil temperature rises above 39°F. During this period, heat is

provided by electric heater instead of by the heat pump.

NOTE

Outdoor heat
exch coil
temp.

Release of defrosting

Start of defrosting

39

°

F

14

°

F

ON

Solenoid coil

(4-way valve)

Compressor

OFF

ON

ON

ON

Electric heater

ON

ON

Fan motor

OFF

OFF

Set speed

YES

YES

Temperature of outdoor heat
exchanger coil is blow 14

°

F.

Temperature of outdoor heat
exchanger coil is higher than
39

°

F.

Defrosting begins

Compressor ON

Release of defrosting

NO

NO

Compressor

OFF

Electric Heater

ON

Heat Pump Model

Model STB0823H1

Advertising