Static resistances, Power exhaust performance, Blower motor and drive data – Sunlife Enterprises SUNLINE DM180 User Manual

Page 33: Table 16: static resistances, Table 17: power exhaust performance, Table 18: blower motor and drive data

Advertising
background image

356214-XIM-A-0108

Johnson Controls Unitary Products

33

* Factory Setting
Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.

TABLE 16: STATIC RESISTANCES

1

DESCRIPTION

RESISTANCE, Pa/IWG

m

3

/s/

CFM

MODEL 180

MODEL 240

MODEL 300

2.1/4500

2.8/6000

3.4/7200

2.8/6000

3.8/8000

4.4/9400

3.78/8000

4.25/9000

4.72/10000

WET COIL

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

25/0.1

25/0.1

25/0.1

GAS HEAT

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

25/0.1

25/0.1

25/0.1

ELECTRIC HEAT OPTIONS

18 KW

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

25/0.1

25/0.1

25/0.1

36 KW

24.8/0.1

50.0/0.2

74.4/0.3

24.8/0.1

50.0/0.2

74.4/0.3

25/0.1

50/0.2

75/0.3

54 KW

50.0/0.2

74.4/0.3

99.2/0.4

50.0/0.2

74.4/0.3

99.2/0.4

50/0.2

75/0.3

100/0.4

72 KW

50.0/0.2

99.2/0.4

149.0/0.6

50.0/0.2

99.2/0.4

149.0/0.6

50/0.2

100/0.4

150/0.6

ECONOMIZER OPTION

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

24.8/0.1

25/0.1

25/0.1

25/0.1

HORIZONTAL DUCT CONNECTIONS

50.0/0.2

74.4/0.3

124.0/0.5

50.0/0.2

74.4/0.3

124.0/0.5

50/0.2

75/0.3

125/0.5

1.

Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table except for Horizontal
Duct Connections.

Add these values due to less airflow resistance.

TABLE 17: POWER EXHAUST PERFORMANCE

MOTOR

SPEED

STATIC RESISTANCE OF RETURN DUCTWORK, IWG

0.2

0.3

0.4

0.5

0.6

CFM

KW

CFM

KW

CFM

KW

CFM

KW

CFM

KW

HIGH*

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

-

-

LOW

4400

0.72

3700

0.74

3000

0.78

-

-

-

-

TABLE 18: BLOWER MOTOR AND DRIVE DATA

MODEL

SIZE

DRIVE

1

BLOWER

RANGE

(RPM)

MOTOR

2

ADJUSTABLE MOTOR PULLEY

3

FIXED BLOWER PULLEY

BELT

(NOTCHED)

kW/HP

FRAME

EFF.

(%)

DESIG-

NATION

PITCH

DIA.

(mm/IN.)

BORE

(mm/IN.)

DESIG-

NATION

PITCH

DIA.

(mm/IN.)

BORE

(mm/IN.)

DESIG-

NATION

PITCH

LENGTH

(mm/IN.)

QTY.

180

High

Static

1030/1240 3.7/5.0

184 T

83

1VP62

109-135

4.3-5.3

29/1-1/8

BK75

175/6.9

25/1

BX68

1773/69.8

1

240

High

Static

895-1080

5.6/7.5

213 T

87

1VP75

140-165

5.5-6.5

35/1-3/8

BK100

239/9.4

30/1-3/16

4

BX81

2103/82.8

1

300

High

Static

950/1130

7.5/10

254 T

89

1LVP58

B70A

157-188

(6.2-7.4)

A2

Bushing

1B5V94

241 (9.5)

B

Bushing

5VX840

2134/84

1

1.

All 50 Hz DM180-300 models come standard with factory filtered High Static Drive.

2.

All motors have a nominal speed of 1450 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because
they are located in the moving air, upstream of any heating device.

3.

Do NOT close this pulley below 1 turn open.

4.

Requires bushing (included in kit).

Advertising
This manual is related to the following products: