Sunlife Enterprises SUNLINE DM180 User Manual

Page 47

Advertising
background image

356214-XIM-A-0108

Johnson Controls Unitary Products

47

9.

If 24 volts is present at the UCB Y1 terminal and
none of the protection switches have opened, the
UCB may have locked out the compressor for
repeat trips. The UCB should be flashing an alarm
code. If not, press and release the ALARMS button
on the UCB. The UCB will flash the last five alarms
on the LED. If the compressor is locked out, cancel
any call for cooling. This will reset any compressor
lock outs.

NOTE:

While the above step will reset any lockouts,
compressor #1 may be held off for the ASCD.
See the next step.

10. If 24 volts is present at the UCB Y1 terminal and

none of the switches are open and the compressor
is not locked out, the UCB may have the compres-
sor in an ASCD. Check the LED for an indication of
an ASCD cycle. The ASCD should time out within
5 minutes. Press and release the TEST button to
reset all ASCDs.

11. If 24 volts is present at the UCB Y1 terminal and

the compressor is not out due to a protective
switch trip, repeat trip lock out, or ASCD, the econ-
omizer terminals of the UCB may be improperly
wired. Check for 24 volts at the Y1 “OUT” terminal
of the UCB. If 24 volts is present, trace the wiring
from Y1 “OUT” for incorrect wiring. If 24 volts is not
present at the Y1 “OUT” terminal, the UCB must be
replaced.

12. For units without economizers:If 24 volts is present

at the Y1 OUT terminal, check for 24 volts at the
Y1 “ECON” terminal. If 24 volts is not present,
check for loose wiring from the Y1 “OUT” terminal
to the Mate-N-Lock plug, the jumper in the Mate-N-
Lock plug, and in the wiring from the Mate-N-Lock
plug to the Y1 “ECON” terminal.

13. For units with economizers: If 24 volts is present at

the Y1 "OUT" terminal, check for 24 volts at the Y1
"ECON" terminal. If 24 volts is not present, check
for loose wiring from the Y1 "OUT" terminal to the
Mate-N-Lock plug, a poor connection between the
UCB and economizer dMate-N-Lock plugs, loose
wiring from the Mate-N-Lock plug to the econo-
mizer, back to the Mate-N-Lock plug, and from the
Mate-N-Lock plug to the Y1 "ECON" terminal. If
nothing is found, the economizer control may have
faulted and is failing to return the 24-volt "call" to
the Y1 "ECON" terminal even though the econo-
mizer is not providing free cooling. To test, discon-

nect the Mate-N-Locks and jumper between the
WHITE and YELLOW wires of the UCB's Mate-
NLock plug. If compressor #1 energizes, there is a
fault in the economizer wiring or economizer con-
trol.

14. The UCB can be programmed to lock out compres-

sor operation during free cooling and in low ambi-
ent conditions. These options are not enabled by
default. Local distributors can test the UCB for this
programming.

For units with factory installed economizers, the
UCB is programmed to lock out compressor opera-
tion when the LAS set point is reached.

For units without factory installed or with field
installed economizers, the UCB allows compressor
operation all the time. This programming can be
checked or changed by the local distributor.

15. If none of the above corrected the error, test the

integrity of the UCB. Disconnect the C1 terminal
wire and jumper it to the Y1 terminal. DO NOT
jump the Y1 to C1 terminals. If the compressor
engages, the UCB has faulted.

16. If none of the above correct the error, replace the

UCB.

On calls for the second stage of cooling, the supply air
blower motor and compressor #1 are operating but
compressor #2 is not (the room thermostat fan switch
is in the “AUTO” position).

1.

If installed, check the position of the economizer

blades. If the blades are open, the economizer is
providing free cooling. If the second stage of
cooling is requested, following a short delay,
compressor #1 will be energized unless it is locked
out. Typically, compressor #2 is energized only
during free cooling if the call for the second stage
of cooling persists for 20 minutes.

2.

Compressor #2 will not energize simultaneously

with compressor #1 if a call for both stages of cool-
ing is received. The UCB delays compressor #2 by
30 seconds to prevent a power surge. If after the
delay compressor #2 does not energize on a sec-
ond stage call for cooling, check for line voltage at
the compressor contactor, M2, and that the contac-
tor is pulled in. Check for loose wiring between the
contactor and the compressor.

Advertising
This manual is related to the following products: