Final installation check, Water connections, Table 6: maximum vent length – STA-RITE SR333LP User Manual

Page 15

Advertising
background image

The terminal must be located (Canada):
• at least 10 feet (3.3M) from any opening into a building.
• at least 12” (.3M) above finished grade or the normally

expected snow accumulation level, whichever is higher

• At least 4 feet (1.2M) horizontally from electric meters,

gas meters, regulators and relief equipment

• At least 7 feet (2.1M) above grade adjacent to walkways

or similar traffic areas.

Allow at least three feet (1M) vertical clearance over vent
termination when terminating under an overhang or deck.
Avoid corners or alcoves where snow or wind could have
an effect. Exhaust may affect shrubbery and some building
materials. Keep shrubbery away from termination. To pre-
vent staining or deterioration, sealing or shielding exposed
surfaces may be required.

8.

Fire Hazard. Do not run the heater vent

into a common vent with any other appliance. Do not
run the Special Gas Vent into, through, or within any
active vent such as a factory built or masonry chimney.

Final Installation Check:

Check that horizontal vent pipe runs slope uniformly at
least 1/4” per foot (2cm per meter) to condensate drain(s).
No sags, no dips, no high or low spots.
Check that vent is supported at elbows, tees, and horizon-
tal and vertical runs according to manufacturer’s instruc-
tions and code requirements.

Check that vent supports and wall and ceiling penetrations
allow free movements up, down, and sideways without
putting any strains on the heater or vent body.
Check for at least six inch (15cm) free air clearance
between the heater vent pipe and combustible materials.
Check that all joints are completely together and sealed.

WATER CONNECTIONS

The heater requires proper water flow and pressure for its
operation. See Figures 15 and 16 for the recommended
installation. The filter pump discharges to the filter, the fil-
ter discharges to the heater, and the heater discharges
directly to the pool or spa.

15

Vent Brand

Wall Thimble

Horizontal Terminal

Vertical Terminal

Saf-T Vent

®

(Part of Vent term.)

5490CI Horizontal Term.

5400 Cap

Saf-T CI Vent

®

(Part of Vent term.)

5490CI Horizontal Term.

5400 Cap

Z-Vent

2SVSWTF04

2SVSTTF04 Tee

2SVSRCF04 Cap

Table 7: Listed Thimbles and Vent Terminals (for Special Gas Vents)

4” Special Gas Vent (Vertical or Horizontal)*

No. of 90° Elbows

Maximum Length in Feet (M)

0

25 Ft. (7.6M)

1

20 Ft. (6.1M)

2

15 Ft. (4.6M)

3

10 Ft. (3.1M)

* Minimum vent length is one foot (.34M), or in accordance with
vent manufacturer’s instructions, and local and national codes.

Horizontal vents 3’ (1M) or less in length do not require a conden-
sate tee, but must slope down toward the outlet at 1/4” to the foot
(2cm/M) to allow condensate to drain.

3" (7.6 cm) Min.,
12" (30.5 cm)Max.
Clearance

Condensate
drain w/Trap

Condensate
Tee

Support
weight
of pipe

Listed
Terminal

Metal Special
Gas Vent
requires
Appliance
Adapter

Metal

Vent

Body

Slope at least
1/4" per foot
(2 cm per Meter)
down towards
condensate drain

FIGURE 14: Typical Special Gas Vent Pipe Installation
(Horizontal-Positive Pressure)

1' Min.

4' Min.

4' Min.

4' Min.

4' Min.

3' Minimum clearance if
horizontal distance to
exhaust opening is less
than 10 feet.

Forced Air
Inlet

Vent
Termination

1' Minimum
above snow or
finished grade
(whichever is
higher)

At least 7'
above grade
adjacent
to public
walkways

Vent
Termination

Vent
Termination

Gas Meter

Max 12"
Min 3"

FIGURE 13: U.S. minimum Exhaust Vent clearances. Local
codes may differ - consult local code officials.

Table 6: Maximum Vent Length