STA-RITE SR333LP User Manual

Page 17

Advertising
background image

17

WATER FLOW RATE

Maximum and minimum water flow rates required by the
heater are listed below:

If the water flow rate to the heater is above 120 GPM (454
LPM), it must be reduced by installing a manual bypass valve
(Figure 17). After installing the valve, adjust the valve to bring
the flow rate within the acceptable range. Then remove the
valve handle or lock it in place to prevent tampering.
Occasionally a two-speed pump will not develop enough
pressure on the low speed to operate the heater. In this
case, run the pump at high speed only to operate the
heater. If this does not solve the problem, do not try to run
the heater. Instead, correct the installation.
Do not operate the heater while an automatic pool cleaner
is also operating. If the circulation pump suction is plugged
(for example by leaves), there may not be adequate flow to
the heater. Do not rely on the pressure switch in this case.

WATER CHEMISTRY

Water chemistry should follow good swimming pool water
chemistry practices. See Table 9 (below) for water chem-
istry parameters.
When using a chlorinator, install it downstream from the
heater and at a lower level than the heater outlet. Install a
corrosion resistant positive seal check valve (see Figure 15)
between the heater and the chlorinator to prevent concen-
trated chemicals from back-siphoning into the heater.
Back-siphoning is most likely to occur when the pump
stops, creating a pressure-suction differential.

Do NOT sanitize the pool by putting chlorine tablets or
sticks into the skimmer(s). When the pump is off, this will
cause a high concentration of chlorine to enter the heater,
which could cause corrosion damage to the heat exchanger.

Model

Minimum Flow

Maximum Flow

200

20 (76)

120 (454)

333

33 (125)

120 (454)

400

40 (152)

120 (454)

Table 9: Water Chemistry Parameters

Disinfectant levels

Minimum

Ideal

Maximum

Free Chlorine, ppm

1.0

2.0-4.0

10.0

Combined Chlorine, ppm

None

None

0.2

Bromine, ppm

2.0

4-6

10.0

Other Sanitizers

Levels not established. Consult local health department before use.

Chemical Values
pH

7.2

7.4-7.6

7.8

Total Alklinity (Buffering), ppm

60

80-100

180

as CaCO3

Total Dissolved Solids, ppm

N/A

N/A

1,500 ppm > TDS at startup*

Calcium Hardness, ppm, as CaCO3

150

200-400

500-1,000

Heavy Metals

None

None

None

Biological Values
Algae

None

None

None

Bacteria

None

None

Refer to Local Code

1. Set Manual
Bypass Valve

2. Remove handle

Cool Water In

Warm Water Out

2680 1096

Inlet from

Filter

Outlet to

Pool

NOTICE: Failure to adhere to the listed water chemistry parameters may result in premature failure of the heat exchanger
and will void the warranty.
*Start-up TDS includes source water TDS and any other inorganic salt added at start-up.

Table 8: Maximum and Minimum

Flow Rate in GPM (LPM)

FIGURE 17: Manual bypass valve

Advertising
This manual is related to the following products: