Figure-4 mounting multiple actuators, Wiring requirements, Control and power leads – Schneider Electric DuraDrive Direct Coupled Actuators MA4X-707X User Manual

Page 18: Table-3 power wiring data

Advertising
background image

18

© Copyright 2010 Schneider Electric All Rights Reserved.

F-26642-8

Wiring Requirements

Control and Power Leads

See Table-3 for power wiring data. Refer to Figure-1 through Figure-3 for typical wiring
applications.

Note: Class 2 control and power lead wiring must be routed separately from line voltage
wiring and any other non-class 2 circuits. Line voltage, auxiliary switch, and auxiliary switch
leads must be connected to a class 1 circuit.

Table-3 Power Wiring Data.

SIEBE

MA-7501-502

AM-673

Figure-4 Mounting Multiple Actuators.

Actuator Voltage

Part Number

Maximum Wire Run in ft. (m) (5% Voltage Drop)

14 AWG

16 AWG

18 AWG

24 Vac

22-30 Vdc

MA4X-7153

330 (101)

200 (61)

130 (40)

MA4X-7153-502

24 Vac

22-30 Vdc

MA40-7043

1100 (335)

700 (213)

440 (134)

MA40-7043-501

24 Vac

22-30 Vdc

MA4X-7073

600 (183)

500 (152)

254 (77)

MA4X-7073-502

Advertising