STUDER

INNOTEC

HP-COMPACT



User manual

HP-COMPACT V3.0 E

13

3 Reserved

4 Program Program mode for Aux.

Contact

5

Contact active Auxiliary Contact is activated

6 Contact

man-

ual

Aux. Cont. manually activated

7

TRANSFER Transfersystem is active. In-

coming voltage is being sent
directly to AC OUT outlet

Transfer (bypass) is disabled
(see chap. 4.7)

8

AC OUT

There is a voltage at the AC
OUT outlet

The Inverter is in Standby-Mode

9

INVERTER

Inverter is working

Forced Inverter Mode (see chap.
4.5)

10

Over Temp.

For the time being the HP-
COMPACT is out of service
because of overheating.

11

Overload

The HP-COMPACT is out of
service because of overload
or short-circuit

12

Batt. Low/High Battery voltage is too low

Battery voltage is or was to high

13

OFF

HP-COMPACT is turned off.
Turning it back on is only pos-
sible manually.

HP-COMPACT is for the time
being turned off. Turning it back
on will follow automatically !

14

EQUALIZE

Battery equalizing is set

15–18

State of charge of the battery LED 15 – Absorption time is run-

ning

25 POWER

MONITOR

Display the value of the output power in % of Pnom (in Inverter
Mode) and the charge current in Amps (in Charger Mode). In this
mode the red LED indicates that power sharing is in use (>100A).

4.3

P

ush buttons

19

ON/OFF

Turning the HP-COMPACT on and off (Help Button for Program-
ming)

20

RESET

Alarm Signal off (Help Button for Programming)

21

Aux. Contact Control Aux. contact (Help Button for Programming)

4.4 Turning

Knobs

22 CHARGER

Adjustment

for

max. Charging Current

23

TRANSFER

Adjustment for Transfer Voltage Threshold (TRANSFER – IN-
VERTER)

24

STANDBY

Adjustment for „Standby“ system

26

INPUT LIMIT Must be adjusted to the maximal available current of your AC

INPUT supply

4.5 The

Inverter

An Inverter is built in the HP-COMPACT, which generates a sinusoidal alternating voltage
of a very high quality. With this Inverter any 230Vac alternating voltage appliance up to the
nominal power of your HP-COMPACT can be operated. Thanks to the generous dimen-
sioning of the HP-COMPACT, you can operate appliances requiring higher power than the
nominal power of the HP-COMPACT for a short time. The HP-COMPACT provides up to
3-times the nominal power to start motors.