2 introduction, Ac input ac output – Studer Innotec HPC4024 User Manual

Page 5

Advertising
background image

STUDER

INNOTEC

HP-COMPACT



User manual

HP-COMPACT V3.0 E

5

Under certain conditions HP-COMPACT or a connected generator can start automatically.
While working on an electrical installation you must ensure that these appliances are dis-
connected beforehand from the installation.

2 Introduction

The HP-COMPACT is a sine wave inverter with integrated battery charger with many addi-
tional functions, it has been developed to be used as stand-alone (no grid-feeding) AC
provider, or as continuous / break-free current supply provider (UPS).
2.1 Principle

schematic


2.2 Description of the main functions
2.2.1 The inverter
The sine wave inverter HP-COMPACT generates a sinusoidal AC voltage with an excep-
tionnlaly precise voltage and stabilized frequency. In order to start large electric motors,
the user has the possibility to use a short surge power which is 3 times the nominal power
of the HP-COMPACT.
The inverter is protected against overload and short-circuit. A power stage with the latest
MOS-FET power transistors, a toroidal transformer, and a fast regulating system makes a
robust and reliable inverter with the highest efficiency. A 1-20 Watt adjustable charge de-
tection system allows the smallest energy consumption and ensures a long life for the bat-
tery.
2.2.2 The transfer system
HP-COMPACT can be connected to an AC source. For example a stand-by emergency
generator or the AC network. With the transfer system, on one side you have an alternati-
ing voltage at the output for the use of consumer appliances. On the other side the battery

6p

8p

AC IN

AUX.
CONTACT

L

PE

N

L

PE

N

OFF

AC OUT

Over Temp.

Overload

AC IN

SOLAR CHARGE

Contact manual

Contact active

Program

COM P A CT

AUXI LIARY CONTACT

ON/OFF

INVERTER - CHARGER

(Select)

RCC-01

INVERTER

CHARGER

(Program)

(Change status)

Battery

Low/High

RESET
ALARM

10

20

30

40

50

60

70

TRANSFER

Char

ge

r

In

v

e

rt

er

5

10

20

40

60

80

100

130

160

A

%

EQUALIZE

RCC-01

BATTERY

CT35

100nF

2,2nF
2,2nF

1uF

1uF

4x2,7MΩ

Remote control

Temp. / remote

power sharing

.

Max. 6m

Max. 40m

AC OUT

Equalize

Transfer delay

RPS-01

RCC-01

CT35

2,2nF
2,2nF

AC Input

AC Output

Temp. sensor

Fuse

Filter

Inverter/
charger

Microprocessor
controlled

Display

Circuit breaker (thermal)

Advertising