The Inverter mode is displayed through LED 9 (Inverter). If the Inverter Mode is disabled
(see chap. 5.5) LED 9 will blink. If the LED 9 is lit, the Inverter is in operation and you have
230Vac at the output AC OUT. The actual power of the connected appliance is displayed
on the power monitor 25 and on the Remote Control.
4.5.1 Charge detection system „Standby“
In order to avoid unnecessary discharge of the battery, the inverter switches OFF auto-
matically if no appliance is connected and switches ON automatically again if appliance is
connected. The LED 8 blinks if the inverter is in Standby-Mode. The switching-on/starting
level can be adjusted with the turning knob 24 „STANDBY”. Adjusting the switching-on
level is as follows: Switch off all consuming devices, turn the Turning Knob 24 to the right
until the LED 8 is blinking, switch on the smallest consuming device (i.e. Mobile phone
charger), turn the Turning Knob slowly to the left until LED 8 is lit.
If the Standby-Mode is not wanted, turn the Turning Knob 24 to the left, to the OFF posi-
tion.
4.5.2 Overload
If the Inverter is too long or too heavily overloaded, it switches off. The LED 11 „Overload“
is lit and LED 13 „OFF“ blinks. After ca. 10 seconds the Inverter switches on automatically.
If the Inverter is overloaded four times one after another in a short time, then it no longer
switches on automatically. The LED 13 remains lit. Press the push button 19 „ON/OFF“ in
order to switch on the Inverter.
4.5.3 Overheating (Over Temp.)
If the Inverter has been overloaded for a long time or it has been working in too high sur-
rounding temperatures, it will switch off. The LED 10 „Over Temp.“ is lit and the LED 13
„OFF“ blinks. After cooling down, the inverter switches back on automatically. One minute
before the inverter switches off for too high temperature it gives out an acoustic alarm sig-
nal. If the Auxiliary Contact has been programmed to detect the high temperature then it
synchronizes the relay with the alarm signal. In this way, for example, an emergency back-
up system can be started without any break in the energy supply.
4.5.4 Battery Condition
Deep discharge of the lead-acid batteries leads to high losses in capacity and early aging.
That is why the battery condition is continuously controlled and supervised. With low volt-
age the inverter switches off. The LED 12 „L/H Batt.“ is lit and the LED 13 „OFF“ blinks.
When the battery voltage gets up to 12.1V / 24.2V / 48.4V, the Inverter switches on auto-
matically. One minute before the Inverter switches off due to low voltage it gives out an
acoustic alarm signal. If the Auxiliary Contact has been programmed to detect the low
voltage then it synchronizes the Aux. Contact with the alarm signal. In this way, for exam-
ple, an emergency back up system can be started without any break in the energy supply.
The low voltage is set to 11.8V / 23.6V / 47.2V. These settings are standard for most bat-
teries. These voltage levels are maintained by the built-in Battery-Management-System of
the HP-COMPACT by matching the load and the battery condition.
This setting is comparable with the levels of 10.8V/ 21.6V / 43.2 which are given for most
batteries at nominal load.
All voltage levels can be programmed. See the instructions under the section on Pro-
gramming. Check with your battery supplier which voltage values should be set.