Self-diagnosis function table – Sanyo AHX0752 User Manual

Page 102

Advertising
background image

5-4

Self-Diagnosis Function Table

1

2

3

4

5

6

7

8

1. Self-Diagnosis Function Table

Alarm code

Alarm meaning

E06

Outdoor unit failed to receive serial communication signals from indoor unit.

E12

Automatic address setting start is prohibited.

E15

Automatic address setting alarm (too few units)

E16

Automatic address setting alarm (too many units)

E20

No indoor units at automatic address setting.

E24

Outdoor unit failed to receive communications from another outdoor unit.

E25

Outdoor unit address setting failure (duplication)

E26

Mismatch in outdoor unit quantity

E29

Outdoor unit failed to receive communication from another outdoor unit.

E30

Outdoor unit serial communications failure

F04

Compressor 1 discharge temperature sensor trouble

F05

Compressor 2 discharge temperature sensor trouble

F06

Gas temperature sensor trouble at outdoor heat exchanger 1

F07

Liquid temperature sensor trouble at outdoor heat exchanger 1

F08

Outdoor air temperature sensor trouble

F12

Compressor intake temperature sensor trouble

F16

High-pressure sensor trouble

F31

Outdoor unit non-volatile memory (EEPROM) trouble

F17

Low-pressure sensor trouble

F23

Gas temperature sensor trouble at outdoor heat exchanger 2

F24

Liquid temperature sensor trouble at outdoor heat exchanger 2

Compressor 3 overcurrent alarm

Compressor 3 lock current alarm

H03

Compressor 1 CT sensor disconnected or short-circuit

Compressor 3 CT sensor disconnected or short-circuit

Compressor 3 discharge temperature sensor disconnected

H06 Low-pressure

trouble

H08

Compressor 1 oil detection sensor (connection) trouble

H13

Compressor 2 CT sensor disconnected or short-circuit

H15

Compressor 2 discharge temperature sensor disconnected

H22

H21

H23

H25

H27

H28

Compressor 3 lock current alarm

H31

HIC trouble alarm

Compressor 2 lock current alarm

L04

Outdoor unit address duplication

L05

Duplicated indoor unit priority (alarm at priority indoor units)

L06

Duplicated indoor unit priority (alarm at non-priority indoor units and outdoor unit)

L10

Outdoor unit capacity not set

L17

Outdoor unit model mismatch

The outdoor unit maintenance remote controller can be used to check the alarm display.

The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm display.
(Refer to “Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.”)

F22

Compressor 3 discharge temperature sensor trouble

H11

Constant speed compressor 2 overcurrent alarm

H12

Constant speed compressor 2 lock current alarm

(DISCH1)

(DISCH2)

(DISCH3)

(EXL1)

(EXG1)

(EXL2)

(EXG2)

(AIR TEMP)

(HPS)

(LPS)

(SCT)

P03

Compressor 1 discharge temperature trouble

L18

4-way valve operation failure.

P04

High-pressure switch activated

P05

Reverse phase (or missing phase) detected, capacity mismatch

P14

O

2

sensor is activated.

P16

Compressor 1 overcurrent

P17

Compressor 2 discharge temp trouble

P18

Compressor 3 discharge temp trouble

P22

Fan motor trouble

P26

Inverter compressor high-frequency overcurrent alarm

P29

Inverter compressor missing phase or lock alarm