W-2way eco-i alarm codes – Sanyo AHX0752 User Manual

Page 78

Advertising
background image

3-16

Trouble Diagnosis

1

2

3

4

5

6

7

8

H31 Alarm

Alarm code

H31

Alarm meaning

HIC trouble alarm

Alarm conditions

This alarm occurs when the microcomputer identifies a trouble signal (indicating abnormal HIC
temperature or other trouble) from the HIC.

Probable cause

Overcurrent in HIC circuit, and resultant abnormal heating, caused by HIC failure

Check

Check the power wiring and connector wiring. If the wiring and connectors are normal, use a
tester to measure the resistance between the compressor HIC power (HIC+) and ground (HIC–).
If there is a short circuit, there is an HIC malfunction.

Correction

If an HIC failure is found, replace the PCB.

Example
Notes

Turn OFF the power, and check the continuity of HIC+ and HIC– on the HIC PCB.

L04 Alarm

Alarm code

L04

Alarm meaning

Outdoor unit refrigerant system address duplication

Alarm conditions

Communication by inter-unit control wiring was received that contained the same address as that
unit 5 times or more within 3 minutes.

Probable cause

Incorrect outdoor system address settings

Check

Check the system address settings again.

Correction

Correct the system address settings.

Example
Notes

Recovery from this alarm occurs automatically (when communication that contains the same
address as that unit is not received for 3 minutes after detection).

The HIC judges the current and temperature, and outputs the trouble signal. In general this
indicates trouble with the HIC itself.

L05 Alarm

Alarm code

L05

Alarm meaning

Duplicated indoor unit priority (alarm at priority indoor units)

Alarm conditions

Multiple indoor units set as the priority unit were detected.

Probable cause

More than one indoor unit is set as the priority unit.

Check

From the wired remote controller, use the indoor unit EEPROM simple settings mode and
check whether or not the value for item code 04 is “0001.”

Correction

If the value of indoor unit EEPROM item code 04 is incorrect, set the correct value from the
wired remote controller.

Example

Notes

This alarm is displayed at the indoor units which are set as the priority unit. At indoor units which
are not set as the priority unit, alarm L06 is displayed.

3. W-2WAY ECO-i Alarm Codes

HIC

-

HIC PCB

HIC +