Sm830157-00_9i, Timer remote controller (rcs-tm80bg) 5/5, Timer remote controller (rcs-tm80bg) – Sanyo AHX0752 User Manual

Page 58

Advertising
background image

2-38

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Remote Control Functions

Table 1 Table of DC Fan Motor Tap Settings (4-way Air Discharge Semi-Concealed type)

Table 2 Table of DC Fan Motor Tap Settings (ceiling-mounted type)

Table 3 Table of DC Fan Motor Tap Settings (1-way Air Discharge Semi-Concealed type)

* Failure to make this setting may result in

decreased airflow and condensation.

3. Timer Remote Controller (RCS-TM80BG)

Selecting the DC fan motor tap
(when setting with the remote controller)

<Procedure>
Stop the system before performing these steps.

Press and hold the

,

and

buttons simultaneously

for 4 seconds or longer.

If group control is in effect, press the

button and select

the address (unit No.) of the indoor unit to set. At this time, the
fan at the indoor unit begins operating.

Use the temperature setting buttons to select item code “5d.”

Press the timer time

/

buttons to select the desired

setting data.

*

For item codes and setting data, refer to Table 1 – Table 4.

Press the

button. (The display stops blinking and remains

lit, and setting is completed.)

*

If air-blocking material is used, use the same procedure as in
steps (3) – (5) above and change the setting for item code “62”
to “0000.”
To change the selected indoor unit, go to step (2).

Press the

button to return to normal remote controller display.

Setting No. Remote controller setting data

Purpose of use, names of accessories

0000

(1) 0001

(3) 0003

(6) 0006

Standard (setting at time of shipping)

High ceiling setting 1 (for standards panel)

Super long-life filter

Oil guard panel

Oil guard panel with raising / lowering grille

Ammonia deodorant filter

Optical regeneration deodorant filter

High ceiling setting 2 (for standards panel)

Ceiling panel with special raising / lowering grille for high locations

High performance filter (90% by JIS colorimetric method)

High performance filter (65% by JIS colorimetric method)

Air cleaning unit

Optical regeneration deodorant filter for air cleaning unit

Deodorant filter

Air-blocking material (for 3-way air discharge)

Air-blocking material (when a discharge duct is connected)

Air-blocking material (for 2-way air discharge)

Setting No. Remote controller setting data

Purpose of use, names of accessories

0000

(1) 0001

(3) 0003

Standard (setting at time of shipping)

High ceiling setting

Super long-life filter

Ammonia deodorant filter (65% by JIS colorimetric method)

Optical regeneration deodorant filter

High performance filter (65% by JIS colorimetric method)

Deodorant filter (65% by JIS colorimetric method)

Setting No. Remote controller setting data

Purpose of use, names of accessories

0000

(1) 0001

(3) 0003

Standard (setting at time of shipping)

Ammonia deodorant filter (65% by JIS colorimetric method)

Deodorant filter (65% by JIS colorimetric method)

Optical regeneration deodorant filter

6

2

1

5

1

4

3

Advertising
This manual is related to the following products: