Warning – Superior SSDVPF-CNE-B User Manual

Page 13

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

13

Securing Screws

(OUTSIDE OF

APPLIANCE)

Insulation

Top Vent

Vent Seal Cap

Firebox Top

Cabinet Top

CROSS SECTION

SIDE VENT SEAL CAP REMOVAL

(SIDE VENT INSTALLATIONS ONLY)

Insulation

Vent Seal Cap

Securing Screws

Side Vent

Cabinet Back

CROSS SECTION

(INSIDE of Appliance)

(OUTSIDE of

Appli

ance)

(INSIDE of

Appli

ance)

WARNING

The VENT SEAL CAP must remain securely installed

on unused vent collar. Failure to do so could result in

leakage of flue products into living space.

Figure 17

Figure 15 -

Figure 16 -

Installation of Vent Restrictor

(Top Vent Installations with Vertical Terminations Only)
A vent restrictor (provided) may be needed with this appliance. If needed,

install the vent restrictor in the appliance top flue outlet as shown in

Figure 17 when vertically terminating the vent system above the roof. It

may be installed either from inside or outside the appliance, in the inner

fireplace collar. It is press-fitted in place.

Note: The restrictor is included within the firebox.

Restrictor

Appliance Top

Vent Outlet

TOP VENT SEAL CAP REMOVAL

(TOP VENT INSTALLATIONS ONLY)

Vent Restrictor

Installation

(Top Vent)

Step 3. INSTALL THE VENT SYSTEM

General Information

These instructions should be used as a guideline and do not supersede

local codes in any way. Install venting according to local codes, these

instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the

USA or the current standards of CAN/CSA-B149.1 in Canada.

Ensure clearances are in accordance with local installation codes and

the requirements of the gas supplier.

Dégagement conforme aux codes d'installation locaux et aux exigences

du foumisseunde gaz.

Use only approved venting components. See Approved Vent

Components on Page 2.

These fireplaces must be vented directly to the outside.

The vent system may not service multiple appliances, and must never

be connected to a flue serving a solid fuel burning appliance. The vent

pipe is tested to be run inside an enclosed wall (such as a chase). There

is no requirement for inspection openings in the enclosing wall at any of

the joints in the vent pipe.

REMOVE VENT SEAL CAP

(From the vent that will be used only)

Top Vent - See Figure 15 and Side Vent - See Figure 16

Preparing the Appliance Vent Collar

Each of the appliances' two vent collars are sealed with a seal cap which

must be removed from the vent collar being used. Refer to Figure 15

for top vent installations and Figure 16 for side vent installations and

the following steps to prepare the appropriate collar for use.

From the vent collar being used, remove the two screws securing the

vent seal cap. Twist the cap counterclockwise. Pull it away from the

appliance and discard, along with the piece of insulation.

Select Venting System - Horizontal or Vertical

With the appliance secured in framing, determine vent routing and identify

the exterior termination location. The following sections describe vertical

(roof) and horizontal (exterior wall) vent applications. Refer to the section

relating to your installation. A list of approved venting components is

shown on Pages 33 and 34.