Spk-500-sl venting installation – Southern Pride SPK-700-SL User Manual

Page 9

Advertising
background image

SPK-500-SL

VENTING INSTALLATION

9/1/04

N

OTE 1. When installing an Oven through a

wall constructed of combustible material, use
the Southern Pride Insulation Kit between
the oven and the wall.

2. The room that the face of the oven is installed
into should have a balanced or positive air pressure.
If the room has negative air pressure, smoke could
escape into the room during operation.

SUPPLIED BY SOUTHERN PRIDE: (*)
Smoke Extractor Damper with 10” chimney adapter plate

SUPPLIED BY CUSTOMER:
6” All Fuel Chimney, 6” Rain Cap, and all accessories
necessary for installation of the 6” chimney.
10” All Fuel Chimney, Exhaust Fan (NOTE: Fan must
be listed for use as a commercial kitchen ventilator),
fan curb, and all accessories necessary for installation
of the smoke extractor system.

ANY VENTILATION SYSTEM MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES. CONSULT WITH

LOCAL OFFICIALS AND A COMMERCIAL KITCHEN VENTILATION CONTRACTOR PRIOR TO INSTALLATION.

HOOD SYSTEM TO INCLUDE:

1. Ventilation Hood
2. Two speed fan (1380/2000)
3. Curb with vented extension and hinge kit
(Specify roof pitch)
4. Grease capture trough
5. Combustion chamber flue vent

SUPPLIED BY CUSTOMER:

6. Duct from hood to fan

VSP HOODS are U/L Listed to the applicable
Southern Pride oven models and are NSF Certified.

SPK-500-SL with recommended
optional VSP Vent Hood System.

THROUGH THE WALL -
DIRECT VENT INSTALLATION

VSP HOOD SYSTEM:

Purchased through Southern Pride

10 ” ALL FUEL SMOKE
EXTR ACTOR CH IMNEY

RAIN
C AP

NOTE: THE SIX INCH ALL FUEL CHIMNEY
SHOULD EX TEND AT LEAST 3’ ABO VE THE
HIGHEST SID E OF THE ROOF OPENING
AND BE AT LEAS T 2’ HIGHER THAN ANY
PORTION OF THE BUILDING WITHIN 10’.
HORIZON TAL.

6” ALL
FUEL
CHIMNEY

EXHAUST
FAN

NOTE: THE 10” ALL
FUEL SMOKE EX-
TRACTOR CHIMNEY
TERMIN ATES AT
THE ROOF C URB

1

2

3

SPECIFY ROOF PITCH

4

5

6

ALL MODELS MAY ALSO BE INSTALLED UNDER A CANOPY HOOD RATED

FOR COMMERCIAL COOKING APPLIANCES.

The oven’s minimum clearances from combustible materials are 18" on left side, 24" on right, 18" on top, 48"

from front, and 2" on back. Minimum clearances are 18" to chimney connector and to smoke extractor chimney
connector. Floor may be constructed of a combustible material. (Note: minimum clearance dimensions are from the
oven cabinet, not from component cover.) (If provision is made for access to service, minimum clearance can be
reduced to 2" on left side.) May be installed through a combustible wall with zero clearance with BBR kit No. 2099.

NOTE: If you have a duct longer than 10 feet or an elbow in your duct
your installation, it may require a larger capacity exhaust fan. Please
specify your duct requirements when ordering the VSP Hood System.

Southern Pride Distributing, L.L.C.

Phone: 618-997-9348

2102 East Main Street - Marion, Illinois 62959

Fax: 618-993-5960

www.southern-pride.com [email protected] [email protected] [email protected]

Sales: 800-851-8180 Service: 800-437-2679 Service Fax: 618-993-0378

Advertising