Chilled-water piping-chilled-water systems only, Figure 8 – Liebert 50 & 60Hz User Manual

Page 21

Advertising
background image

Site Preparation and Installation

13

Chilled-Water Piping—Chilled-water Systems Only

Refer to Figure 8 for recommended field installed hardware such as shut-off valves and hose bibs.
Chilled-water supply and return lines must be insulated to prevent condensation.
The minimum recommended water temperature is 42°F. Connection sizes are 1-1/4" FPT.

Figure 8

General arrangement diagram - chilled-water systems

Bleed Valve

Chilled Water Coil

Chilled Water
Control Valve

Female Adapters

Chilled
Water
Supply

Chilled
Water
Return

** Shutoff Valves

** Hose Bibs

3 - Way Chilled Water
Control Valve
(Optional)

FIELD PIPING

FACTORY PIPING

* Field piping refers to the use of hard
piping using sweat adapter kit
or precharged line set.

Supply

Return

** Components are not supplied by
Liebert but are recommended for
proper circuit operation and
maintenance.

DPN000236_Rev0