1 location considerations, 2 piping connections, Water/glycol piping considerations – Liebert 50 & 60Hz User Manual

Page 35: Condensing unit fluid requirements, Regulating valve, 3 electrical connections, Control connections, Location considerations, Piping connections, Electrical connections

Advertising
background image

Site Preparation and Installation

27

2.7

Indoor Water- and Glycol-Cooled Condensing Unit Installation

2.7.1 Location Considerations

The condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of

concern, the condensing unit should be located away from personnel. Normal operating sound may be

objectionable if the condensing unit is placed near quiet work areas.
To mount the unit in the ceiling, refer to 2.4 - Installing the Evaporator or Chilled-Water Units.

2.7.2 Piping Connections

Details for Refrigerant (R-22) Loop piping are in 2.4.3 - Piping Connections and Coolant

Requirements.

Water/Glycol Piping Considerations

Refer to Figure 20 for recommended field installed piping hardware such as shut-off valves and hose-

bibs. Water filters should be installed if water quality is poor. Filters will extend the service life and

efficiency of the condensers.

Condensing Unit Fluid Requirements

The maximum fluid pressure is 150 psi standard pressure or 350 psi for high pressure units (Refer to

unit serial tag and model number description page at beginning of this manual).

Regulating Valve

Water/Glycol-cooled units include a coolant flow regulating valve which is factory adjusted and should

not need field adjustment.
Standard water pressure and high water pressure valves are adjusted differently. Contact Liebert

Service before making any adjustments.

2.7.3 Electrical Connections

Refer to 2.4.4 - Electrical Connections, Evaporator or Chilled-Water Unit for general wiring

requirements and cautions. Refer to electrical schematic when making connections. Refer to serial tag

for full load amp and wire size amp ratings.

Control Connections

A six-wire control connection is required from the evaporator unit to the water/glycol condensing unit.

Two (2) additional wires are required when hot gas bypass is ordered. Glycol-cooled units also

require a two-wire control connection to the drycooler and pump package.

NOTE
HVAC grade ethylene or propylene glycol should be used on glycol systems.

Automotive antifreeze must not be used.

Advertising
This manual is related to the following products: