Lennox Hearth ELITE CI2000HT User Manual

Page 10

Advertising
background image

10

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

Figure 5 - Types of Chimney

Types of Chimneys

The unit must be connected to either a code-approved masonry chimney

with a flue liner, or a 6 inch diameter factory-built chimney complying with

the requirements for Type HT chimneys in the standard UL 103.

The chimney is a vital part of your stove installation. A properly built

masonry chimney or a properly installed factory-built chimney will assure

a consistent draft under a variety of weather conditions (a smoking

stove is usually caused by a chimney problem). The stove flue size is

6 inches diameter, which is approximately 28 square inches minimum.

The maximum flue size should be no more than three (3) times the cross

sectional area of the size of the stove flue collar. In this case, that would

be no larger than an 10-inch diameter stack, or approximately 85 square

inches maximum.

All chimneys must be installed as specified by local building codes and

according to the chimney manufacturer instructions (in the case of

a factory-built chimney). See the chimney manufacturer instructions

for exact specifications. Factory-built chimneys must comply with UL

103HT or ULC S629. A chimney connector shall not pass through an attic

or roof space, closet or similar concealed space, or a floor, or ceiling.

Where passage through a wall, or partition of combustible construction

is desired, the installation shall conform to CAN/CSA-B365, Installation

Code for Solid-Fuel-Burning Appliances and Equipment.

Factory

Built

Chimney

Tile-lined Masonry Chimney

Minimum / Maximum Flue Diameter:

Minimum 6”, Maximum 10”

Chimney Connector Adapter

Use a chimney connector adapter to connect the chimney connector up

to the chimney. The small ends of the chimney connector should all point

down for a drip free installation. Position all seams toward the back for

aesthetics. The chimney connector must be 6-inch diameter.

Secure adjoining sections of chimney connector to each other using three

equally spaced sheet metal screws. Secure the connector pipe to flue

collar using three equally spaced sheet metal screws. DO NOT secure

chimney connector to chimney with screws.

Connection To A Factory-built Chimney

This space heater is to be connected to a factory-built chimney conforming

to CAN / ULC – S629, Standard for 650°C Factory-Built Chimneys. All pipe

connections must be sealed (ie. high temperature silicone).

For Reduced Residential Clearances Using Double Wall Pipe (Approved

for Model CI2000HT Only):

Type L and listed double wall connector pipe is acceptable. Install any fac-

tory-built brand of pipe according to the manufacturer’s instructions.

Vapor Barrier at Chimney Penetration

Install all venting components per the Vent Manufacturers installation

instructions. Ensure that there is an effective vapor barrier at the location

where the chimney penetrates to the exterior of the structure. This can

be accomplished by applying a non-hardening waterproof sealant to the

following components:

• Around the chimney at the point where the storm collar will meet the

chimney just above the Flashing

• Along the vertical seam of the chimney pipe, where it is exposed to

the weather.

• On each nail head on the flashing.

• Around the chimney at the point where the storm collar will meet the

chimney just above the flashing.

Notes:

• On a flat or tarred and graveled roofs, nail and seal the flat roof flashing

to the roof on all sides with roofing compound.

• Do not put screws through the flashing into the chimney pipe.

Chimney Inspection

Existing chimneys must be inspected before installing your stove. Con-

sult your local building department for chimney code requirements. A

masonry chimney must have a code approved liner. This liner must not

have broken or missing pieces. Some non-code masonry chimneys may

be brought up to code by being relined. (Consult your dealer or qualified

chimney sweep). Factory-built chimneys should also be inspected, first

for creosote deposits (which should be removed), and then for integrity

of the stainless steel liner. Look for obvious bulges in the lining, which

may indicate the need to replace that section (use a bright flashlight).

Also, inspect the attic to see that the chimney has proper clearance to

combustible framing members. For interior masonry chimneys and most

factory-built chimneys, this must be a two (2) inch air space clearance,

which must not be filled with insulation or any other material. An exterior

masonry chimney must have a one (1) inch air space clearance.

Acceptable Connector Pipe For Installations

When Using Single Wall Pipe: Install a six (6) inch diameter, single wall,

24 MSG black steel or 26 MSG blued steel connector pipe on the flue

collar of the unit. When installing pipe, the crimped ends of the pipe

should all point down. Position all seams toward the back for aesthet-

ics. Three (3) pre-drilled holes are provided in the flue collar for fasten-

ing the pipe securely to the stove. Use sheet metal screws to do this.

Additional sections of single wall pipe should be fastened together with

at least three (3) sheet metal screws each section. All pipe connections

must be sealed (ie. high temperature silicone). When connecting to the

factory-built ceiling support package, use the manufacturer’s transition

piece, usually called a dripless connector, to join single wall pipe to their

factory-built chimney section.

When Using Approved Double Wall Pipe (Approved for Model CI2000HT

Only)

Type L and listed double wall connector pipe is acceptable. Install any

factory-built brand of pipe according to the manufacturer’s instructions.

All pipe connections must be sealed (ie. high temperature silicone).

INSTALLATION

Advertising