Lennox Hearth ELITE CI2000HT User Manual

Page 7

Advertising
background image

7

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

Note: For Floor Protection Material Requirements in USA and Canada

see Floor Protection Using Alternate Material As Floor Protector on

this page.

Floor Protection - Model CI2000HT (USA and Canada)

The floor protector must meet or exceed the minimum thermal require-

ments as defined on this Page (see Floor Protection / Hearth Extension

Using Alternate Material As Floor Protector). If the floor protection is

to be stone, tile, brick, etc., it must be mortared or grouted to form a

continuous noncombustible surface. If a chimney connector extends

horizontally over the floor, protection must also cover the floor under

the connector and at least 2” (51 mm) to either side.

The floor protector must fully cover the area beneath the appliance and

extend 18” to the front, 5”-USA and 8”-Canada to the sides, and 0”-USA

and 8”-Canada from the back as shown in Figure 2.

USA - 0 “ (0 mm)

Canada - 8” (203 mm)

Minimum

USA - 5” (127 mm)

Canada - 8” (203 mm)

Minimum

Top View

Figure 2

- Floor Protection Size Requirements, Model CI2000HT

USA - 5” (127 mm)

Canada - 8” (203 mm)

Minimum

USA - 18” (457 mm)

Canada - 18” (457 mm)

Minimum

Floor

Protector

Stove Back

Stove Front

Floor Protection / Hearth Extension Using Alternate Material As

Floor Protector - Model CI2000HT (USA and Canada)

Note: Also see Floor Protection above .

The hearth pad or alternate material used as a floor/hearth protector must

be constructed of a durable noncombustible material having an equal or

better thermal conductivity value (lower k value) of k =.84 BTU/IN FT2

HR °F or a thermal resistance that equals or exceeds r = 1.19 HR °F FT2

IN/BTU with a minimum thickness of 1/2”. With these values, determine

the minimum thickness of the alternate material required using the

formula(s) and shown in Table 3.

Note: Any noncombustible material having a minimum thickness of 1/2”

(13 mm) whose k value is less than .84 or whose r value is more than

1.19 is acceptable. If the alternate material used has a higher k value

or lower r value will require a greater thickness of the material used. In

some cases, if the k value is less or the r value higher, a thinner material

may be used.

Minimum

k-value (per Inch) of

Specified min.

thickness of = alternate material (k

M

) x

thickness

alternate

k-value (per inch)

of listed

material (T

M

)

of listed material (k

L

)

material (T

L

)

T

M

(inches) =

k

M

x

T

L

*.84

T

M

(inches) = *1.92 x

.5"

*.84

1.143 (inches)= 2.286

x

.5"

Answer - The minimum required thickness of the Durock is 1.143" therefore

round up to nearest standard thickness available which is 1-1/4."

Minimum

r-value (per Inch)

Specified min.

thickness of = of listed material

x

thickness

alternate

r-value (per inch)

of listed

material

of alternate material

material

T

M

(inches) =

r

L

x

T

L

r

M

T

M

(inches) = *1.19 x

.5"

* .52

1.144 (inches)= 2.288

x

.5"

Answer - The minimum required thickness of the Durock is 1.143" therefore

round up to nearest standard thickness available which is 1-1/4."

Using the r formula:

Methods of determining floor protection equivalents:

To determine the thickness required for the alternate material when

either the "k" value or "r" value is known, use either the k formula or r

formula.

Example: If Durock™ Cement Board is to be used for the floor protection,

how thick must this material be?

k

M

= k value per inch of alternate material

r

M

= r value per inch of alternate material

T

M

= minimum thickness required for alternate material

T

S

= standard thickness of the alternate material

k

L

= k value per inch of listed material

r

L

= r value per inch of listed material

T

L

= minimum thickness of listed material

Note: An asterisk "*" indicates, it is a value taken from Table 3.

Using the k formula:

Advertising