NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

3) Drill a hole in the vent pipe per the draft gauge manufacturers instruc-

tions (to create a draft test port). Note: Hole location should be a

minimum of 1 foot above flue outlet collar.

4) Start a fire (See How To Start And Maintain A Fire on Page 15).

5) After the fire is well established (20-25 minutes) and burning at a low

setting, perform the draft test per the gauge manufacturer instructions.

The draft gauge should read between .05 and .06” W.C. (inches water

column). Excessive draft (above .06 W.C.I.) can result in too much

combustion air to be pulled into the firebox, this will produce hotter

burns and could result in overfiring. Too little draft (below .05” W.C.)

will not allow enough combustion air delivery to maintain a fire well

or cause performance problems such as smoking (this may result in

improper operation of appliance, i.e. will not maintain fire well unless

fuel door is left open).

6) Install a screw to seal the draft test port in the vent pipe. If the draft

test reading was not within the required range, correct the installation

and repeat this procedure.

Ventilation Requirements / Provide Adequate Air For Combustion

THE FRESH AIR REQUIREMENTS OF THIS APPLIANCE MUST BE MET

WITHIN THE SPACE WHERE IT WILL BE INSTALLED. VENTILATION IS

ESSENTIAL WHEN USING A SOLID FUEL BURNING HEATER.

In well insulated and weather tight homes, it may be difficult to establish

a good draft up the chimney (caused by a shortage of air in the home).

The lack of air is caused by many common household appliances which

exhaust air from the home (such as a furnace, heat pump, air conditioner,

clothes dryer, exhaust fans, fireplaces, and other fuel burning appliances).

Also, the combustion process of this heater uses oxygen from inside the

dwelling. If the available fresh air delivery in the dwelling is insufficient

to support the demands of these appliances, problems can result (i.e.

excessive negative pressure can develop in the dwelling which will affect

the rate at which this appliance can draft thus resulting in performance

problems; See Draft Requirements on Page 11). To correct this problem

it may help to open a window (preferably on the windward side of the

house) or install a vent to provide make-up air into the dwelling.

Important Notes:

• Minimize the use of elbows (30°, 45° or 90°) - Offsets in the venting

system are very restrictive and will inhibit the draft (i.e. You will lose

approximately 5 feet of effective draft for every 90 degrees of direction

change). This appliance requires 12 to 15 feet of effective draft for

optimum performance (see Draft Requirements on Page 11).

• First section of pipe must be vertical - Use as much straight vertical

pipe directly above the appliance as possible before using an elbow

(a 2’ to 3’ initial vertical rise is suggested).

• See pipe manufacturers instructions for installation requirements of

venting components and vent clearances.

Chimney

Termination

Cap

Storm

Collar

Roof

Flashing

Ceiling Support

Assembly

Slip

Adapter

Chimney

Connector

6” x 24” 24-gage

black steel or 26 gage

blued steel single

wall pipe

Single Wall Pipe

Using 6” Diameter Single Wall Connector Pipe

Figure 7 - Single Wall Pipe