3.5.2 UPS Configuration Screen

Review Settings

Follow this procedure to review your UPS configuration settings. Follow the menus below by pressing

and

to review the settings.

Main Menu

UPS Status

> UPS Configuration

Display Date/Time

Event Log

Active Alarms

Transfer to Bypass

Module Replacement

Service Tools

UPS Configuration

UPS Configuration

> Review Settings

Change Settings

Service Mode

Review Settings

Voltage

Frequency

Battery

Alarms

Service Contact

Auto Restart

UPS Shutdown Delay

Remote Shutdown

External Battery

Bypass Alarm Mode

Intelli-Battery Ca.

Air Filter Reminder

Guarantee Shutdown

External Battery

External batt config

Amp.Hr

0000

Charge (A) 00.0

Bypass Alarm Mode

Bypass Alarm Mode

Mode:

Enable

Intelli-Battery Ca.

Intelli-Batteries

0

Air Filter Reminder

Air Filter Reminder

Mode:

26 weeks

Guarantee Shutdown

Guarantee Shutdown

Mode: Enable/Disable

Voltage

Voltage Settings

Input 210

Output 210

Frequency

Frequency Settings

Frequency Hz: 50/60

Sync Range Hz: +/- 5.0

Slew Range Hz/S: 3.0

Battery

Battery Settings

Test intrvl weeks: 2

on Wed 06:00

Low Batt Warn:2 min

Alarm

Alarm Settings

Redundant Alarm:

Enabled/Disabled

Max Load: Enabled/Disabled

Service Contact

Service Contact

Liebert Corp.

www.liebert.com

Auto Restart

Auto Restart

Mode:

Disable

Batt %

0%

Delay

10

UPS Shutdown Delay

UPS Shutdown Delay

120 seconds

Remote Shutdown

Remote comm shutdown

Mode: Enable

Review Settings menu options