Operating Instructions

25

Set Date/Time: Allows user to enable/disable DST

(Daylight Saving Time), change the Day, Date and

Time setting on Nfinity. When enabled, the time will

automatically adjust to Daylight Saving Time.

Max Load Alarm Set: Allows an alarm to set when

Nfinity’s load reaches a specific level.

UPS Shutdown Delay: Delays UPS shutdown for

specified amount of time after receiving shutdown

command via relay contacts only.

Redundant Alarm Set: Sets Alarm to notify user

when redundancy is no longer available.

Service Contact: Set a contact for the user to reach

if problems occur.

Remote Shutdown: Enables / Disables the Remote

Communications Shutdown.
If you are using MultiLink™ software, this parameter

should be enabled in order for the UPS output to be

turned off once the operating system has been shut-

down.

External Battery: Sets total amp-hour for external

batteries to provide a more accurate runtime remain-

ing value on the LCD display and through communi-

cations.

When using the Non-Modular External Battery

Cabinets with Chargers (P/N: PB10SLF105WC120),

enter the following:

Set Time/Date

DST Mode

Set Time/Date

DST Mode

DST Mode

Enabled

* Disabled

Set Date/Time

Date/Time

MM/DD/YYYY

HH:MM:SS

Max Load Alarm Set

Mode

Threshold

Alarm Mode

Max Load Alarm Mode

* Enable

Disable

Threshold

Max Load Alarm Set

Threshold kVA = xx.x

UPS Shutdown Delay

xxx seconds

Redundant PWR Alarm Set

Enable

* Disable

# Cabinets

AH Value

Charge Current

1

0091

07.0

2

0182

14.0

3

0273

21.0

4

0364

28.0

5

0455

35.0

6

0546

42.0

Service Contact

>Company Name

Company Phone

Company Name

Company/Name

LIEBERT CORP.

Phone Number

Phone Number

WWW.LIEBERT.COM

Remote Shutdn

* Enable

Disable

External Battery

Amp-hour

> Charge Current

External Batt Config

Enter total amp-hour

0000

External Batt Config

Enter charge current

00.0