Operating Instructions

23

Change Configuration Settings - Change Settings Menu

Starting from the Main Menu, locate and press UPS Configuration. From the UPS Configuration

screen, select the Change Settings option. You may configure Nfinity from a large variety of selec-

tions. Items indicated by an asterisk (*) are the selected settings.

Frequency: Sets the output frequency.

Frequency Sync Range: Sets the window to which

the system synchronizes to the input supply.

Frequency Slew Rate: Sets the rate of change of

frequency through the sync range window.

Set Password: Set a Password to prevent unautho-

rized users from changing the configuration of the

Nfinity. It can be up to seven characters in length.

Once set, the password will be required to change the

configuration.

Main Menu

UPS Status

> UPS Configuration

Display Date/Time

Event Log

Active Alarms

Transfer to Bypass

Module Replacement

Service Tools

UPS Configuration

UPS Configuration

Review Settings

> Change Settings

Service Mode

Change Settings

Frequency

Frequency Sync Range

Frequency Slew Rate

Set Password

Auto Battery Test

Low Battery Warning

Auto Restart

User Settings

Set Date/Time

Max Load Alarm Set

UPS Shutdown Delay

Redund Alarm Set

Service Contact

Remote Shutdown

External Battery

Bypass Alarm Mode

Intelli-Batt Ca.

Air Filter Reminder

Guarantee Shutdown

Line Compensation

Factory Defaults

Output Frequency

50 Hz

* 60 Hz

Frequency Sync Range

0.5 Hz

1.0 Hz

2.0 Hz

3.0 Hz

4.0 Hz

* 5.0 Hz

NOTE
If the password is lost, call Liebert Technical

Support.

Frequency Slew Rate

0.5 Hz

1.0 Hz

2.0 Hz

3.0 Hz

4.0 Hz

* 5.0 Hz

Set Password

xxxxxxx