4.2

Module LED Indication

Every Battery, Power and Control Module features two LEDs to help inform the user of the module

status, as shown below left. Refer to Table 2 for details.

Table 2

Guide to LEDs

Status

LED

(Green)

Fault

LED

(Yellow)

Module Status

OFF

OFF

Module not inserted into

frame. System is OFF.

OFF

ON

Module is initializing

(max 30 seconds*).

FLASHING

OFF

Normal Operation

FLASHING

FLASHING

Module is in start-up

qualification mode or module

warning. **

FLASHING

ON

Module failed and is off-line.

OFF

FLASHING

Abnormal operation,

re-insert module.

ON

OFF

ON

ON

ON FLASHING

* If this persists for more than 30 seconds, check to verify the

lever is in the down position, otherwise the module is faulty.

** If both green and yellow LEDs are flashing for more than 30

seconds, then reinsert module.

Green Status LED
Yellow Fault LED

Control Module