Operation, Auxiliary power operation – Lincoln VANTAGE 500 User Manual

Page 25

Advertising
background image

CV-WIRE MODE

Connect a wire feeder to the Vantage and set welder controls
according to the instructions listed earlier in this section.

The Vantage in the ”CV-WIRE” position, permits it to be used with
a broad range of flux cored wire (Innershield and Outershield)
electrodes and solid wires for MIG welding (gas metal arc
welding). Welding can be finely tuned using the “ARC
CONTROL”. Turning the ARC CONTROL clockwise from -
10(soft) to +10(crisp) changes the arc from soft and washed-in to
crisp and narrow. It acts as an inductance/pinch control. The
proper setting depends on the procedure and operator
preference. Start with the knob set at 0.

For any electrodes, including the above recommendations, the
procedures should be kept within the rating of the machine. For
additional electrode information, See www.lincolnelectric.com or
the appropriate Lincoln publication.

ARC GOUGING

For optimal performance when arc gouging, set the Vantage
“WELD MODE” switch to the “CC - STICK” position, and the
“ARC CONTROL” to 10.

Set the “OUTPUT” knob to adjust output current to the desired
level for the gouging electrode being used according to the
ratings in the following table:

* Maximum current setting is limited to the Vantage maximum of

575 Amps.

PARALLELING

When paralleling machines in order to combine their outputs, all
units must be operated in the CC-STICK mode only at the same
output settings. To achieve this, turn the WELD MODE switch to
the CC-STICK position. Operation in other modes may produce
erratic outputs, and large output imbalances between the units.

AUXILIARY POWER OPERATION

Start the engine and set the IDLER control switch to the desired
operating mode. Full power is available regardless of the welding
control settings, if no welding current is being drawn.

The auxiliary power of the Vantage consists of two 20 Amp-
120VAC (5-20R) GFCI duplex receptacles and one 50 Amp-
120/240 VAC (14-50R) receptacle. The 120/240VAC receptacle
can be split for single phase 120 VAC operation.

The auxiliary power capacity is 12,000 watts of 60 Hz, single
phase power. The auxiliary power capacity rating in watts is
equivalent to volt-amperes at unity power factor. The maximum
permissible current of the 240 VAC output is 50 A. The 240 VAC
output can be split to provide two separate 120 VAC outputs with
a maximum permissible current of 50 A per output to two separate
120 VAC branch circuits. Output voltage is within ± 10% at all
loads up to rated capacity.

NOTE: The two 120V GFCI receptacles and the two 120V circuits
of the 120/240V receptacle are connected to different phases and
cannot be paralleled.

The auxiliary power receptacles should only be used with three
wire grounded type plugs or approved double insulated tools with
two wire plugs.

The current rating of any plug used with the system must be at
least equal to the current capacity of the associated receptacle.

SIMULTANEOUS WELDING AND AUXILIARY
POWER LOADS

It must be noted that the above auxiliary power ratings are with
no welding load. Simultaneous welding and power loads are
specified in table B.4. The permissible currents shown assume
that current is being drawn from either the 120 VAC or 240 VAC
supply (not both at the same time).

ELECTRODE

CURRENT RANGE

DIAMETER

(DC, electrode positive)

(1/8”)

30-60 Amps

(5/32”)

90-150 Amps

(3/16”)

200-250 Amps

(1/4”)

300-400 Amps

(5/16”)

350-450 Amps

(3/8”)

450-575 Amps*

B-8

OPERATION

B-8

Vantage 500 CUMMINS

Advertising