Wiring, Feed-through panel: feed and load wiring – Lutron Electronics Switch User Manual

Page 10

Advertising
background image

R

10

Installation Guide for Switching Panels

• Use a trough when the switching panel is far away from the distribution panel. Splice neutrals in trough.
• Wire the switching panel similar to a lighting distribution panel. Run feed and load wiring.
• Use the switching panel to provide temporary lighting by leaving the bypass jumpers in place. (See page 16 for

more details.)

N

N

H

H

H

SH

H

SH

H

SH

H

SH

Control Circuit Power:

• Supplies power for internal operation.
• Requires dedicated feed with same

voltage and phase as panel.

• Must be 1/4" (6 mm) away from

PELV (Class 2: USA) control wiring
harness.

• Panel voltage (see pages 2-3)

indicates feed voltage.

• For 230 V

and 240 V

panels,

“Hot” is referred to as “Live”.
Therefore, terminals will be labeled L
and SL.

PELV

(Class 2:

USA)

wiring

entrance

Bypass jumpers:

do not remove

Load

Distribution

panel

Terminal block

Neutral

Ground

Dedicated

hot/live

Feed-Through Panel: Feed and Load Wiring

Power feed

(hot/live)

Switched
hot/live

Load

neutral

Typical load circuit

Control

circuit

power

Wiring

{

277 V

277 V

N

N

N

120 V

277 V

control

feed

120 V

control

feed

OR

120 V

*

277 V

Ground

Ground

Neutral

Neutral

Do not wire to

these terminals

Dual-Voltage Panel: Feed and Load Wiring (120/277 V

only)

XINT8-120FT shown

Wire to either the

120 V

or the 277

V

control feed

terminals, not both.
The terminals for the
unused voltage will
remain empty.

Wire Sizes

• Power Feed (Hot/Live):

#14-#10 AWG (2.5-4.0 mm

2

)

• Switched Hot/Live:

#14-#10 AWG (2.5-4.0 mm

2

)

Circuit
breaker

*Note:

120 V

Hot/Live

terminal is protected by
an internal fuse in case

277 V

is mistakenly

applied. A spare fuse is
also supplied in the panel
terminal block.