Wiring, Continued) – Lutron Electronics Switch User Manual

Page 12

Advertising
background image

R

12

Installation Guide for Switching Panels

Wiring

(continued)

L
SL
N
L
SL
N
L
SL
N
L
SL
N

Panel with Isolation Switch: Feed and Load Wiring
(230/220-240 V

only)

Bypass jumpers -

do not remove

Load

Ground bus

Main feeds:
Phase A, B, C, and Neutral

Wiring Tips

• Wire the switching panel similar

to wiring a lighting distribution
panel.

• Run feed and load wiring. No

other wiring or assembly
required.

The switching panel can provide

temporary lighting:

• Wire all loads.
• Leave the bypass jumpers in

place.

• Use branch circuit breakers at

the distribution panel to switch
lights on and off.

Wire Sizes

230 V

#14-#2 AWG (2.0-35 mm

2

)

220-240 V

#14-#10 AWG (2.0-4.0 mm

2

)

Switched Hot/Live

#14-#10 AWG

(2.5-4.0 mm

2

)

Load Neutral

#14-#10 AWG

(2.5-4.0 mm

2

)

Typical

switch leg

Advertising