Panel Mounting

Panel and TUB Mounting

Mounting Guidelines

• For Indoor Use Only! NEMA, Type 1 enclosure, IP20.
• Large and extra-large panels for surface mount only.
• Panel generates heat. Mount where ambient

temperature is 32-104 ºF
(0-40 ºC).

• Relative humidity must be <90% non-condensing.
• Reinforce wall structure for panel weight and local

codes; see table.

• Mount panel where audible noise is acceptable.

(Internal relays click.)

• Mount panel so line (mains) voltage wiring is at least

6 feet (1.8 m) from audio or electronic equipment and
associated wiring.

• Mount within 7º of true vertical.
• Consult Dimensions page for dimensions, conduit

knockouts, and mounting holes and hardware.

• Install in accordance with all national and local

electrical codes.

Surface Mounting

• Lutron recommends using

1/4 in. (6 mm) mounting
bolts (maximum size
accepted by keyholes).

• Allow room for cover. Leave

1 1/2 in. (38 mm) clearance
to each side of panel.

Recess Mounting

• Mount panel between flush

and 1/8 in. (3 mm) below
finished wall surface.

• Allow room for cover. Leave

1 1/2 in. (38 mm) clearance
to each side of panel.

Distribution
panel
(if feed-
through)

Feed wiring
and
switch legs
to loads

PELV
(Class 2: USA)
wiring

Feed wiring

and

switch legs

Side View:

Surface Mount

Side View:

Recess Mount

Front View

R

8

Installation Guide for Switching Panels

Maximum Panel Weights
Mini

30 pounds (13.9 kg)

Standard

80 pounds (37 kg)

Large

135 pounds (61.3 kg)

Extra-Large

200 pounds (90.7 kg)

Recommended Mounting Heights*

(120/277/347 V

Softswitch128 systems)

Mini

45 in. (1143 mm)

Standard

25 in. (635 mm)

Large

10 in. (254 mm)

Extra-Large

7 in. (178 mm)

*Measure from floor to bottom of panel.

Provides optimal viewing height for controller.

Softswitch128
(XPS)
entry

GRAFIK
Systems
(XP)
entry