Panel with Branch Circuit Breakers: Feed and Load Wiring
(120/277/347 V

only)

Bypass jumpers -

do not remove

Load

Neutral bus

Neutral bus

Main lugs

Branch circuit

breakers for

temporary

lighting

Wiring Tips

• Wire the switching panel similar

to wiring a lighting distribution
panel:

• Run feed and load wiring. No

other wiring or assembly
required.

The switching panel can provide

temporary lighting:

• Wire all loads.
• Leave the bypass jumpers in

place.

• Use branch circuit breakers at

the distribution panel to switch
lights on and off.

Wire Sizes

120 V

#4 AWG to 250 KCMIL (MCM) (25-185 mm

2

)

277 V

#4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm

2

)

347 V

#4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm

2

)

Feed Wiring

Switched Hot/Live
#14-#10 AWG
(2.5-4.0 mm

2

)

Load Neutral
#14-#10 AWG
(2.5-4.0 mm

2

)

Typical switch leg