Installation, Technical specifications – cv-655 – Lincoln Electric CV-655 User Manual

Page 10

Advertising
background image

A-1

CV-655

A-1

INSTALLATION

TECHNICAL SPECIFICATIONS – CV-655

Volts at Rated Amperes

44

44

Auxiliary Power

See the OPERATION section

for Auxiliary Power

information by model

Amps

650

815

Maximum Open Circuit Voltage

48

Duty Cycle

100% Duty Cycle

NEMA Class I (100)*

60% Duty Cycle

Current Range

70-815

INPUT - THREE PHASE ONLY

OUTPUT

* European models meet IEC974-1 standards.

1Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers which have a delay in tripping action that decreases as the magnitude of the current increases.

RECOMMENDED INPUT WIRE AND FUSE SIZES

Standard

Voltage

230/460/60

230/460/575/60

208/416/60

460/60
575/60

230/400/50/60*
380/500/50/60*

440/50/60

200/400/50/60

415/50/60

Code

Number

10120
10121
10122
10123
10124
10125
10126
10127
10128
10129

100% Duty Cycle

94/47

94/47/38

104/52

47
38

94/54
56/43

49

107/54

52

60% Duty Cycle

116/58

116/58/47

128/64

58
47

116/67

69/53

60

132/67

64

Input Current at Rated Output

RATED OUTPUT

INPUT

VOLTAGE /

208
230
416
460
575
200
230
380
400
415
440
500

TYPE 75°C

(SUPER LAG)

OR BREAKER

SIZE (AMPS)

1

200 Amp
175 Amp

90 Amp
90 Amp
70 Amp

200 Amp
175 Amp
100 Amp
100 Amp

90 Amp
90 Amp
80 Amp

TYPE 75°C

GROUND WIRE

IN CONDUIT

AWG(IEC-MM

2

) SIZES

6 (14)
6 (14)

8 (8.4)
8 (8.4)
8 (8.4)

6 (14)
6 (14)

8 (8.4)
8 (8.4)
8 (8.4)
8 (8.4)
8 (8.4)

TYPE 75°C

COPPER WIRE

IN CONDUIT

AWG(IEC-MM

2

) SIZES

40°C (104°F) Ambient

1 (43)
2 (34)
6 (14)
6 (14)

8 (8.4)

1 (43)
2 (34)
6 (14)
6 (14)
6 (14)
6 (14)

8 (8.4)

INPUT AMPERE

RATING ON

NAMEPLATE

104

94
52
47
38

107

94
56
54
52
49
43

HERTZ

FREQUENCY

60
60
60
60
60

50/60
50/60
50/60
50/60
50/60
50/60
50/60

PHYSICAL DIMENSIONS

HEIGHT

27.5 in

699 mm

WIDTH

22.2 in

564 mm

DEPTH

38.0 in

965 mm

WEIGHT

652 lbs.

283 kg.