Site Preparation

12

2.3

Refrigerant Planning Values

Planning for the refrigerant requirements of the completed system is the addition of the charges from

Indoor Unit, Condenser (including Lee-Temp receiver, if used) and the interconnecting piping.

Tables 3 and 4 provide the approximate charge required for the condensers and the interconnecting

piping. Consult indoor unit manuals for indoor unit charge requirements.
These values can be used for obtaining adequate refrigerant for the system, but should not be used for

final charging. Consult indoor unit manual for charging procedures.
Table 3

R-22 and R-407C refrigerant required, approximate

Standard

Condenser

Models

Approximate R-22 Refrigerant Needed

Approximate R-407C Refrigerant Needed

Single Circuit

lb (kg)

Dual Circuit

lb/circuit (kg/circuit)

Single Circuit

lb (kg)

Dual Circuit

lb/circuit (kg/circuit)

FSC or

VFD

Lee-Temp

(includes

receiver)

FSC or

VFD

Lee-Temp

(includes

receiver)

FSC or

VFD

Lee-Temp

(includes

receiver)

FSC or

VFD

Lee-Temp

(includes

receiver)

83

5 (2.3)

27 (12.3)

3 (1.4)

15 (6.8)

5 (2.3)

26 (11.8)

3 (1.4)

15 (6.8)

104

8 (3.6)

39 (17.7)

7 (3.2)

21 (9.5)

8 (3.6)

37 (16.8)

7 (3.2)

20 (9.0)

165

15 (6.8)

53 (24.0)

5 (2.3)

27 (12.3)

15 (6.8)

50 (22.7)

5 (2.3)

26 (11.8)

205

20 (9.1)

76 (34.5)

7 (3.2)

38 (17.2)

19 (8.6)

72 (32.7)

7 (3.2)

36 (16.3)

251

19 (8.6)

75 (34.0)

10 (4.6)

38 (17.2)

18 (8.2)

71 (32.23)

10 (4.6)

36 (16.3)

308

29 (13.2)

113 (51.3)

11 (5.0)

58 (26.3)

28 (12.7)

107 (48.5)

11 (5.0)

55 (24.9)

415

54 (24.5)

182 (82.6)

15 (6.8)

75 (34.0)

51 (23.1)

173 (78.4)

15 (6.8)

71 (32.2)

510

72 (32.7)

N/A

30 (13.6)

149 (67.6) 68 (30.8)

N/A

29 (13.2)

142 (64.4)

616

N/A

267 (121.3)

27 (12.3)

113 (51.3)

N/A

254 (115.2)

26 (11.8) 108

(49.0)

830

N/A

N/A

30 (13.6)

149 (67.6)

N/A

N/A

29 (13.2)

142 (64.4)

1010

N/A

N/A

60 (27.2)

154 (69.9)

N/A

N/A

57 (25.9)

147 (66.7)

Quiet-Line Condenser Models

63

N/A

39 (17.7)

N/A

21 (9.5)

N/A

37 (16.8)

N/A

20 (9.1)

119

N/A

50 (22.7)

N/A

27 (12.3)

N/A

48 (21.8)

N/A

26 (11.8)

127

N/A

76 (34.5)

N/A

38 (17.2)

N/A

72 (32.6)

N/A

36 (16.3)

143

N/A

126 (57.2)

N/A

64 (29.0)

N/A

120 (54.5)

N/A

61 (27.7)

214

N/A

161 (73.0)

N/A

81 (36.7)

N/A

153 (69.4)

N/A

77 (34.9)

286

N/A

196 (88.9)

N/A

125 (56.7)

N/A

186 (84.4)

N/A

119 (54.0)

409

N/A

N/A

N/A

129 (58.5)

N/A

N/A

N/A

125 (55.8)

572

N/A

N/A

N/A

196 (88.9)

N/A

N/A

N/A

186 (84.4)

Table 4

Interconnecting piping refrigerant charge

Line Size,

O.D., in.

R-22, lb/100 ft. (kg/30m)

R-407C, lb/100 ft. (kg/30m)

Liquid Line

Hot Gas Line

Liquid Line

Hot Gas Line

3/8

3.8 (1.7)

3.7 (1.7)

1/2

7.3 (3.3)

6.9 (3.1)

5/8

11.7 (5.3)

2.1 (1.0)

11.0 (5.0

2.2 (1.0)

3/4

16.6 (7.5)

3.0 (1.4)

15.7 (7.1)

3.1 (1.3)

7/8

24.4 (11.1)

4.4 (2.0) 23.0

(10.4) 4.5

(1.9)

1-1/8

41.4 (18.9)

7.8 (3.5) 39.3

(17.8) 7.8

(3.5)

1-3/8

63.3 (28.7)

11.8 (5.4) 59.8

(27.1 11.8

(5.4)

1-5/8

16.7 (7.6)

16.7 (7.6)

Advertising