Installation – Lincoln Electric COMMANDER IM544-B User Manual

Page 13

Advertising
background image

A-6

INSTALLATION

COMMANDER 400

A-6

2. Take necessary steps to assure load is limited to the

capacity of the Commander by installing a 45 amp,
240 VAC double pole circuit breaker.

Maximum

rated load for each leg of the 240 VAC auxiliary is 45
amperes.

Loading above the rated output will

reduce output voltage below the allowable -10% of
rated voltage which may damage appliances or
other motor-driven equipment and may result in
overheating of the Commander 400 engine.

3. Install a 50 amp 120/240 VAC plug (NEMA Type 14-

50) to the double-pole circuit breaker using No. 6, 4
conductor cable of the desired length. (The 50 amp,
120/240 VAC plug is available in the optional K802R
plug kit.)

4. Plug this cable into the 50 Amp 120/240 Volt recep-

tacle on the Commander 400 case front.

Figure A.2 Connection of the Commander 400 to Premises Wiring

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 8 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

45AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE