OPERATION

B-10

AUXILIARY POWER OPERATION

Start the engine and set the IDLER control switch to
the desired operating mode.

Full power is available

regardless of the welding control settings, if no welding
current is being drawn..

The auxiliary power of the Commander consists of two-
120VAC (5-15R) duplex receptacles with GFCI protec-
tion and one 120/240 VAC (14-50R) receptacle. The
120/240VAC receptacle can be split for single phase
120 VAC operation.

The auxiliary power capacity is 10,000 watts of 60 Hz,
single phase power. The auxiliary power capacity rat-
ing in watts is equivalent to volt-amperes at unity power
factor. The maximum permissible current of the 240
VAC output is 44 A. The 240 VAC output can be split to
provide two separate 120 VAC outputs with a maximum
permissible current of 44 A per output to two separate
120 VAC branch circuits. Output voltage is within ±
10% at all loads up to rated capacity.

NOTE: The 240V receptacle has two 120V outlets of
different phases and cannot be paralleled.

The auxiliary power receptacles should only be used
with three wire grounded type plugs or approved dou-
ble insulated tools with two wire plugs.

The current rating of any plug used with the system
must be at least equal to the current capacity of the
associated receptacle.

SIMULTANEOUS WELDING AND AUXIL-
IARY POWER LOADS

It must be noted that the above auxiliary power ratings
are with no welding load. Simultaneous welding and
power loads are specified in table B.4. The permissible
currents shown assume that current is being drawn
from either the 120 VAC or 240 VAC supply (not both at
the same time).

COMMANDER 400

Welding

Output Range

Setting

50-575

400
270
230
180
120

90

Welding Output

500A/40V
400A/36V
270A/31V
230A/29V
180A/27V
120A/25V

90A/24V

Permissible

Power - Watts

(Unity Power

Factor)

None
None

3000
6000
7500
9500
9500

Permissible

Current in

@120 V ±10% *

0
0

28

56**
70**
88**
88**

Auxiliary
Amperes

@ 240 V ±10%

0
0

14
28
35
44
44

* Each GFCI duplex receptacle is limited to 15 amps.
** Not to exceed 44 A per 120 VAC branch circuit when splitting the 240

VAC output.

TABLE B.4 Commander 400 Simultaneous Welding and Power

Loads