E™ Power System User Manual

Part Number: PN380C


CAUTION:

ALWAYS FOLLOW NEC GUIDELINES AND YOUR LOCAL COMPANY
PRACTICES WHEN SELECTING DC WIRING AND PROTECTION.

Table 5: Minimum Recommended DC AWG for 90°C Cabling for Unprotected Outputs

shows

recommended wire sizes based on ampacity. The maximum current rating for the chassis is 100 A

.

Re

ct

ifi

e

rs

Single hole bulk

battery connections

(¼" studs)

14 GMT Fuse

Connections

14

1

2

Figure 3: DC Wire Diagram

Each chassis is equipped with 14 GMT style fuse connections and an unfused bulk DC connection
located on the rear of the chassis. The GMT fused connections are made on “lugless” terminal blocks
with compression screws. The terminal blocks will accept wire sizes up to 12AWG.

The bulk DC connection may be used as a battery input or as an unfused bulk output. The connections
require a terminal lug (1/4” single hole lug with a max tongue width of 0.63” or less), such as PANDUIT
part # LCA4-14-L. Size wires based on the total rectifier capacity and choose conductor size according to

Table 5: Minimum Recommended DC AWG for 90°C Cabling for Unprotected Outputs

.

Connecting to a DPoE™ Power Patch Panel or Compact 8 Midspan

Each DP

O

E™ Power over Ethernet System is shipped with a keyed power connector harness and two

butt splices (PANDUIT part # BSV14X) for use in connecting the panel to the power source. The butt
splices included with the DP

O

E™ Power Patch Panel will support 14 - 16 AWG solid or stranded wire.

WARNING:

Connect each separate DP

O

E™ Power Patch Panel or Compact 8 Midspan to the

rear of the DP

O

E™ Power System using one of the 14 GMT-fused outputs per

panel.

Do not wire multiple untis to a single output on the DP

O

E™

Power System.