DP

O

E™ Power System User Manual

Part Number: PN380C

Butt splices connectors

Power connector
housing with wire leads

48VDC
Supply

Power Connector on rear side of
DP

O

E™ Power Patch Panel or

Compact 8 Midspan

Connector
pinouts

Figure 4: Connecting to a DPoE™ Power Patch Panel or Compact 8 Midspan

NOTE:

The included power harness has two wires for the A-feed power only (pins 1 & 2).
The DP

O

E™ Power Patch Panel or Compact 8 Midspan supports an optional

redundant B-feed power option, but the terminals and wire leads are not attached to
the power harness.

Contact PANDUIT Technical Support for more information about connecting the
redundant B-Feed power. (PANDUIT part # DPOEPWRDUAL should be used for
redundant powering options)

WARNING:

The power supply connections on the DP

O

E™ Power Patch Panel and the

Compact 8 Midspan are polarized. They will not function if power is wired
improperly.

Table 5: Minimum Recommended DC AWG for 90°C Cabling for Unprotected

Outputs

Total Rectifier Current Rating (A)

Wire and Lug Gauge

(AWG) using 90

°

C wire

(NEC Table 310.16)

1

10 16
20 14
25 12



1

Table 310.16 uses Table 3B – Sizes of Conductors from BS EN 60950:2000, “Safety of Information

Technology Equipment,” December 2000 for non-building wiring.