7

Torque Settings

The following table shows recommended torque settings for all mechanical and electrical connections
according to screw or nut size in inch pounds (in-lbs).

Table 6: Recommended Torque Settings

Screw or Nut Size

Toque (in-lbs)

4-40 6
6-32 12
8-32 22

10-32 37
12-24 50

¼-20 65

Required Tools

The DP

O

E™ Power System is designed to be installed with commonly available tools:

• #1 & #2 flat blade and Phillips head screwdrivers

• Torque wrench

• 7/16” socket, ¼” drive

• Wire and cable strippers (PANDUIT part number CT-100)

• Wire and cable crimpers (such as PANDUIT part CT-1550, CT-1551, CT-1570, CT-1700

Contour Crimp

TM

Controlled Cycle Crimp Tools) (used for optional bulk DC connection)

Site and Equipment Preparation

Prior to unpacking the DP

O

E™ Power System, note any physical package damage that could indicate

potential damage to the contents. After removing the DP

O

E™ Power System from the boxes and packing

material, inspect for shipping and/or other damage. Any problems should be reported to PANDUIT
technical support.

Table 7: PANDUIT Corp. Contact Information

PANDUIT Technical Support

Fax:

1-708-444-6993

E-mail: [email protected]

PANDUIT Product Installation Instructions

www.panduit.com/resources/install_maintain.asp

Worldwide Subsidiaries and Sales Offices

www.panduit.com


Have all tools, wire, cables, hardware, etc., within easy reach. To the extent possible, ensure a clean
(free of debris, dust, foreign material, etc.) work environment. Care should be taken in the installation
process to prevent wire clippings from getting into the equipment.

NOTE:

If possible, the rectifiers should remained sealed in their shipping boxes until the
chassis wiring is complete. Rectifiers should not be inserted until all DP

O

E™

components are properly connected.

Advertising